4

20 mA DC input

(Model VY513_)

Precautions

 

Power transformer is shared   
If a power transformer is shared by two products, 
connect the terminal 

 of each actuator to the 

transformer with the same polarity. Connect the 
terminal 

 in the same way.  

 

 

It the terminals are connected with different polarities, 
the product may break down  (see Fig. 22) .

 

Control signals are shared for 4–20 mA DC 
input 

      

The 4–20 mA DC input signals of this product 
are not isolated from the power.  

 

And, the input impedance of 4–20 mA DC 
signals is 100 Ω. The relations among the input 
impedance of the product, the output load 
resistance of the controller, and the output load 
resistance and input impedance of an isolator  (if 
necessary)  must meet the following formula.  
’Applicable load resistance’ > ‘Total of input 
impedance’  

     

If two products are operated by one controller, 
configure the system referring to Fig. 23 for two 
individual transformers, Fig. 21 for a shared 
transformer. To share a power transformer, install 
an isolator to the 4–20 mA DC input terminals of 
the second product. Otherwise, the product will 
malfunction.

Input signals and power are shared

Model R35TC0,

Model R36TC0

ACTIVAL

4-20 mA DC input

 (Model VY513_)

Isolator


2

3

3

1

1



2
3
4
5
6
7

ACTIVAL

4-20 mA DC input

 (Model VY513_)

Isolator

(mandatory)

Power

suppply

2

1



2
3
4
5
6
7

*

1  Provide an isolator for the controller that is not internally 

isolated.

*

2  Terminals 2, 5, and 7 are internally connected.

*

3  Refer to notes under “Power transformer is shared.”

Figuar 21 

Power is shared

Model R35TC0,

Model R36TC0

ACTIVAL

4-20 mA DC input

 (Model VY513_)

Isolator


2

1

Isolator

1

1



2
3
4
5
6
7

Model R35TC0,

Model R36TC0

ACTIVAL

4-20 mA DC input

 (Model VY513_)

Power

supply


2

1



2
3
4
5
6
7

*

1  Provide an isolator for the controller that is not internally 

isolated.

*

2  Terminals 2, 5, and 7 are internally connected.

Figuar 22 

Input signals are shared

Model R35TC0,

Model R36TC0

ACTIVAL

4-20 mA DC input

 (Model VY513_)

Isolator


2

1

1

3

1



2
3
4
5
6
7

ACTIVAL

4-20 mA DC input

 (Model VY513_)

Isolator

Power

supply

Power

supply

2

1



2
3
4
5
6
7

*

1  Provide an isolator for the controller that is not internally 

isolated.

*

2  Terminals 2, 5, and 7 are internally connected.

*

3  Provide an isolator if no isolator is provided to the 4–20 

mA DC input of the first actuator AND the applicable load 

resistance of controller is less than 200 Ω.

Figuar 23 

Summary of Contents for ACTIVAL SCS13A

Page 1: ...mostat Model TY9800 4 20 mA DC input Provides proportional control in combination with a DDC controller e g Infilex GC Model WY5111 Model R35 R36 2 10 V DC input Provides proportional control in combi...

Page 2: ...equency of use as basic parameters The recommended design life of this product is 10 years The recommended design life assumes that maintenance such as replacement of the limited life parts is carried...

Page 3: ...125 CAUTION After installation make sure no fluid leaks from the valve pipe connections Improper piping may cause fluid leakage outside of the valve Do not put a load or weight on this product Doing s...

Page 4: ...ers 1 Total resistance Nominal 1 k Operation range 0 fully closed to 100 fully open Max applied voltage 5 V DC Note It cannot be connected with Model M904E Valve flange adapter kit 4 Valve size Major...

Page 5: ...on location Indoor use Note Salt air corrosive gas flammable gas and organic solvent must be avoided Outdoor use Note Salt air corrosive gas flammable gas and organic solvent must be avoided And use t...

Page 6: ...mperature of fluid Chilled hot water 0 175 C Note When using the stainless steel valve with chilled water of 0 C or lower please contact Azbil Corporation 175 C steam 0 175 C 200 C steam 0 200 C Flow...

Page 7: ...tion applied for the 4 20 mA DC input and 2 10 V DC input Output voltage range 2 V DC fully closed to 10 V DC fully open Maximum load resistance 10 k or more max output current 1 mA Valve position Ind...

Page 8: ...maintenance 2 For setting the auxiliary switch make sure to allow a clearance of 300 mm or more Figuar 1 Dimensions mm Table 1 Dimension table mm Valve size L L1 H H1 D C t h N DN15 108 50 213 75 95 7...

Page 9: ...For setting the auxiliary switch make sure to allow a clearance of 300 mm or more Figuar 2 Dimensions mm Table 2 Dimension table mm Valve size L L1 H H1 D C g t h N DN15 108 50 213 75 95 70 51 12 15 4...

Page 10: ...AB 6464 10 Parts Indication Actuator Yoke Valve body Pointer Terminal cover Top cover Knockout hole Top lid Top cover Joint Stem Gland packing Seat ring Plug Figuar 3 Parts Indication...

Page 11: ...ve install it on the pipe diverting sections for each piping group Do not install this product near a steam coil hot water coil etc High temperature radiant heat may cause failure of the actuator Avoi...

Page 12: ...he factory CAUTION After installation make sure no fluid leaks from the valve pipe connections Improper piping may cause fluid leakage outside of the valve Do not put a load or weight on this product...

Page 13: ...te A special sheet is inserted between the yoke and valve for heat insulation When you changed the mounting position be careful not to lose the sheet 4 Make sure that the groove on the tip of the valv...

Page 14: ...y of the power supply and 2 10 V DC feedback signal and then correctly wire the product Incorrect wiring may result in PCB print circuit board burnout z z How to maintain IP54 dust proof splash proof...

Page 15: ...terminals 4 to 7 Note Correctly connect the wires referring to Fig 9 to Fig 13 Terminals Connection Fig 14 to Fig 27 Wiring Examples and Advanced Wiring Examples 4 Mount the terminal cover and attach...

Page 16: ...troller V Voltage between 4 and 6 Figuar 10 z z Nominal 135 resistance input Model VY512_J 4 5 6 7 To controller 24 V AC power Open Open R B W T2 T1 1 3 2 Figuar 11 z z 4 20 mA DC input Model VY513_J...

Page 17: ...put Model VY513_ Model R35 Model R36 ACTIVAL 4 20 mA DC input Model VY513_ 4 5 6 7 T1 T2 1 2 1 3 2 Power transformer Model AT72 J1 100 200 V AC 1 The terminal 2 power terminal 5 4 20 mA DC input and t...

Page 18: ...ce life the minimum opening position cannot be maintained Avoid instrumentation that may cause secondary dam age in case of abnormality Figuar 18 Using relay interlock ACTIVAL Nominal 135 resistance i...

Page 19: ...duct will malfunction Input signals and power are shared Model R35TC0 Model R36TC0 ACTIVAL 4 20 mA DC input Model VY513_ Isolator 2 3 3 1 1 2 3 4 5 6 7 ACTIVAL 4 20 mA DC input Model VY513_ Isolator m...

Page 20: ...ed 2 Terminals 2 5 and 7 are internally connected 3 Refer to notes under Power transformer is shared Figuar 24 Power is shared Model WY5117 Model WY5117 ACTIVAL 2 10 V DC input Model VY514_ Isolator 2...

Page 21: ...ON Do not put a load or weight on this product Doing so may damage the product Before doing maintenance be sure to turn off the power to this product Failure to do so may result in electric shock or d...

Page 22: ...rminals Check the wirings Leakage is observed when the valve is fully closed Pointer position when the valve is fully closed Fully close the valve Abnormal sound or vibration is observed Check that le...

Page 23: ...AB 6464 23 This blank page was added for page layout purposes...

Page 24: ...al and Electronic Equipment Directive RoHSD EMCD EN 61000 6 2 EN 55011 Class A Group 1 RoHSD EN 50581 ACTIVAL is a trademark of Azbil Corporation Infilex is a trademark of Azbil Corporation Specificat...

Reviews: