AB-6464
17
Wiring Examples
z
Nominal 135 Ω feedback potentiometer
(Model VY511_)
①
②
③
④
⑤
⑥
⑦
Controller
Infilex GC
(Model WY5111)
100/200 V AC
Power transformer
(Model AT72-J1)
ACTIVAL
Nominal 135 Ω feedback
potentiometer
(Model VY511_)
CLOSE(0)
OPEN(100)
AC24V
~
4
5
6
7
OPEN
CLOSE
1
3
2
Figuar 14 Connection to Infilex GC
z
Nominal 135 Ω resistance input
(Model VY512_)
Proportional controller
(Model TY900_Z)
ACTIVAL
Nominal 135 Ω
resistance input
(Model VY512_)
~
4
5
6
7
T
1
~
T
2
⊥
W
B
R
1
3
2
OPEN(100)
CLOSE(0)
W
B
R
Power transformer
(Model AT72-J1)
100/200 V AC
Figuar 15 Connection to Neostat
z
4
–
20 mA DC input
(Model VY513_)
(Model R35, Model R36)
ACTIVAL
4-20 mA DC input
(Model VY513
_
)
~
4
5
6
7
T
1
~
T
2
⊥
+
-
+
*
1
*
2
-
+
-
1
3
2
⑬
⑭
Power transformer
(Model AT72-J1)
100/200 V AC
*
1 The terminal 2 (power), terminal 5 (4–20 mA DC input),
and terminal 7 (2–10 V DC feedback signal) are internally
connected.
*
2 Input impedance of 4–20 mA DC input of the actua-
tor is 100 Ω.
4–20 mA DC input is not isolated. Install the power trans-
former separately.
Figuar 16 Connection to R-series
z
2
–
10 V DC input
(Model VY514_)
ACTIVAL
2-10 V DC input
(Model VY514
_
)
~
4
5
6
7
T
1
~
T
2
⊥
(
+
)
(com)
+
-
+
-
1
3
2
Controller
Infilex AC
(Model WY5117)
Power transformer
(Model AT72-J1)
100/200 V AC
*
*
Terminals 2, 5, and 7 are internally connected.
Note: Do not implement a daisy chain wiring passing through
the actuator’s power terminals.