Solar power balance:
When enabled, solar input
power will be
automatically adjusted
according to the
connected load power.
Solar power balance
enable (Default):
If selected, solar input power will be
automatically adjusted according to
the following formula:
Max. input solar power = Max.
battery charging power +
Connected load power.
Solar power balance
disable:
If selected, the solar input power
will be the same as max. battery
charging power no matter how
many loads are connected. The
max. battery charging power will be
based on the setting current in
program 02.
(Max. solar power = Max. battery
charging power)
32
Bulk charging time
(C.V stage)
(Only available for
4KVA/5KVA model)
Automatically (Default):
If selected, inverter will judge this
charging time automatically.
5 min
The setting range is from 5 min to
900 min. Increment of each click is 5
min.
900 min
If “USE” is selected in program 05, this program can be set up.
33 Battery
equalization
Battery equalization Battery equalization disable (default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
34
Battery equalization
voltage
4KVA/5KVA default setting: 58.4V. Setting range is from 48V ~
58.4V. Increment of each click is 0.1V.
35
Battery equalized time
60min (default)
Setting range is from 5min to 900min.
Increment of each click is 5min.
36
Battery equalized timeout
120min (default)
Setting range is from 5min to 900 min.
Increment of each click is 5 min.
37
Equalization interval
30days (default)
Setting range is from 0 to 90 days.
Increment of each click is 1 day
39
Equalization activated
immediately
Enable
Disable (default)