When the phase angle between L1 and L2 is 0°.
MLV 5KW
L1
N
Grid
connection
Load
Output
L1
N
L2
L2
L1
L2
N
L1
N
120V
120V
120V
120V
L2
208V
208V
When the phase angle between L1 and L2 is 120°.
MLV 5KW
L1
N
Grid
connection
Load
Output
L1
N
L2
L2
L1
L2
N
L1
N
120V
120V
120V
120V
L2
240V
240V
When the phase angle between L1 and L2 is 180°.
Please follow below steps to implement AC input/output connection:
1.
Before making AC input/output connection, be sure to open DC protector or disconnector first.
2.
Remove insulation sleeve 10mm from the six conductors. And short-circuit phase L and neutral conductor N
3 mm.
3.
Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be
sure to connect PE protective conductor (
)
first.
→
Ground (yellow-green)
L1
→
LINE (black)
L2
→
LINE (brown)
N
→
Neutral (blue)