UMAXTC20CO V1.1.1 Preliminary Documentation – May be Subject to Change 48-59
Entry Description
Sub-Index 0h
Access RW
PDO Mapping
No
Value Range
-10000.0 to 10000.0
Default Value
4368.0 (-273°C * 16)
3.4.11. Object 3130h: Cold Junction Input Process Value
This read-only object represents the scaled value of the measured cold junction temperature.
Object Description
Index 3130h
Name
Cold Junction Input Process Value
Object Type
VAR
Data Type
FLOAT32
Entry Description
Sub-Index 0h
Access RO
PDO Mapping
Yes
Value Range
-32768 to 32767
Default Value
No
3.4.12. Object 4000h: Low Temperature Warning Threshold
This object sets the low threshold of the normal operating temperature range for each
thermocouple’s input field value ($6100.) Any FV value below this limit flags a low warning in the
corresponding thermocouple’s status byte ($6150), as well as setting an EMCY code in the pre-
defined error field ($1003). The data in sub-indexes 1 to 4 is interpreted with a fixed resolution of
0.1°C/bit.
Object Description
Index 4000h
Name
Low Temperature Warning Threshold
Object Type
ARRAY
Data Type
INTEGER16
Entry Description
Sub-Index 0h
Description Largest
sub-index supported
Access RO
PDO Mapping
No
Value Range
4
Default Value
4