![Axi STS 6003 Instruction, Operating, & Maintenance Manual Download Page 21](http://html1.mh-extra.com/html/axi/sts-6003/sts-6003_instruction-operating-and-maintenance-manual_3036309021.webp)
REV03016704010220
20
13.
Open the inlet and outlet ball valves on the system.
14.
Press the Alarm Reset button on the enclosure door panel to acknowledge the alarm and reset it, if needed.
15.
Return the selector switch to its original position and check for leaks when re-starting and pressurizing the
system.
Servicing the Fine Filter
Clogged filter elements restrict the flow of fuel, resulting in the system’s pressure gauge indicating a pressure spike. The
gauge is mounted between the pump and the fine filter. At a pressure of 22 PSI, the pump will automatically shut off and
generate a High Pressure Alarm. This signal indicates that it is time to change the filter element.
Changing the fine filter(s):
1.
Turn the enclosure door panel selector switch to the “OFF” position – making sure the pump will not turn on.
2.
Close the inlet and outlet ball valves.
3.
Place an appropriate container underneath the filter.
4.
Remove the old spin-on filter with a filter wrench.
5.
Apply a film of lubricating oil to the gasket of the new filter. Screw the new filter canister to the filter head until the
gasket is tight and secure (rotate the element an additional 0.5-1.0 turn after the filter makes contact with the
gasket).
6.
Open the inlet and outlet ball valves.
7.
Push the Alarm Reset button on the enclosure door panel to acknowledge the alarm and reset it.
8.
Return the enclosure door panel selector switch to its original position.
9.
Check for leaks when re-starting and pressurizing the system.
Note: Disposal of fuel, associated waste, and filters must be in accordance with all applicable federal, state, and local
rules, laws, standards, and regulations.
!WARNING!: Some fuels may have been treated with biocides. Biocides are extremely toxic and may enter the
body through the skin. It is recommended to use adequate protection and proper precautions if the fuel at-hand
contains biocide type products.
Replacement Filter Chart
STS SERIES FILTERS
All Filters are absolute, unless otherwise noted | wb: waterblock | SS: Stainless Steel Screen
Cartridge Filters
Spin-On Filters
10
µ
30
µ
60
µ
SS
3
µ
3
µ
WB
10
µ
10
µ
WB
25
µ
3
µ
X-Glass
STS 6000 SX-F/6003/7003
01010
01030
01060S
FF-3
WB-3
FF-10
WB-10
FF-25
FFZ-3
Sts 6004/7004
01810
01830
01860s
FF-3
WB-3
FF-10
WB-10
FF-25
FFZ-3
Sts 6010/7010
04010
04030
04060S
FF-3
WB-3
FF-10
WB-10
FF-25
FFZ-3
Auto Water Drain (AWD) –
If Applicable
Servicing Auto Water Drain Strainer:
1.
Turn the enclosure door panel selector switch to the “OFF” position – making sure the pump will not turn on.
2.
Close the system’s Inlet and Outlet Isolation Ball Valves.
3.
Place a fuel waste container below the strainer and Manual Drain Port.
4.
Ensure the AWD’s Isolation Ball Valve is closed by opening the Manual Drain Port.
5.
Open the bleed screw on top of the Water Separator to break vacuum.
6.
Remove and clean the AWD’s strainer.
7.
Reattach and secure the strainer to the AWD assembly.
8.
Continue to “Servicing Water Collection Drum”.
Summary of Contents for STS 6003