Commissioning/Initial Start-Up 

Gauge Venting 

After shipment, gauge pointers may not rest at zero due to internal case pressure build-up, which is caused by 
temperature and/or pressure variations. As a result, their accuracies may be significantly reduced.  To restore the gauges 
to operating condition, move the yellow lever of the fill plug to the open position or remove the black rubber piece from top 
of gauge and leave it open to vent. 

Switch Adjustments 

Note: Please contact AXI International before adjusting either the vacuum or the pressure switch to avoid voiding the 
system’s warranty.  

 
Vacuum and Pressure Switches 

When the value exceeds the set point of the switches’ rating, the switch will change state. Ensure you are working with a 
normally closed position (leads on opposite sides of the switch – across from one another are connected to the wire 
spades). If the set point is incorrect, adjustments can be performed in the field as follows: 
 

1.

 

Remove the two wires connected to the normally closed spades on the top of switch. 

2.

 

Pop off the “Rubber Plug” in between the spades on top of the switch. 

3.

 

Insert a 5/64” Allen Wrench/Key into the slot. 

4.

 

For a vacuum switch, adjust the Wrench/Key 

¼

 - 

½

 turn at a time CCW to increase the vacuum alarm’s set point. 

5.

 

For a pressure switch, adjust the Wrench/Key 

¼

 - 

½

 turn at a time CW to increase the pressure alarm’s set point. 

6.

 

After adjusting the settings, perform the testing procedure(s) for the switch(es) as outlined in the commissioning 
section. 

 

Flow Switch 

When the flow rate drops below the predetermined set point on the flow switch (i.e. 10 GPM), the switch will trigger a 
signal to shut down the pump. If the set point is incorrect, an adjustment can be performed in the field as follows: 
 

1.

 

Loosen the lock screw on the stem of the flow switch using the provided Hex Allen Key 

2.

 

Rotate the setting dial on the flow switch until the desired GPM flow range printed on the stem is reached.  

a.

 

If the Orange LED light on the Flow Switch’s M12 Connector is not illuminated, a flow rate lower than its 
set point is being detected.  

b.

 

Turn the black neck of the Flow Switch CW. Once the point is reached where the Orange LED light turns 
on, turn the dial one more full turn CW. 

3.

 

Tighten the lock screw to secure the setting dial’s placement 

4.

 

After adjustment, ensure to perform the relevant testing procedure outlined below 

 

Note: For information on factory set points or timer delays please refer to the “Accessories and Additional Configuration 
Parameters” subsection in the “Technical Assistance and Ordering” section. 

Internal Pressure Relief Adjustment 

Note: Please consult AXI International before performing any internal pressure relief settings to avoid warranty issues  

 
The pump used on the STS systems come from the factory with a pre-set internal pressure relief bypass. If the pressure 
on the discharge of the pump rises past this set point, the internal bypass will open and recirculate the fuel in the head of 
the pump to protect the itself and any downstream components. When this happens, the discharge branch of the system 
will not see the proper fuel flow, most likely causing the system to fail on a low flow alarm.  
 

Summary of Contents for STS 6003

Page 1: ...Dr Fort Myers FL 33905 239 690 9589 Toll Free 877 425 4239 FAX 239 690 1195 www AXI International com STS STS 6003 7003 Instruction Operating Maintenance Manual ENCLOSED FUEL MAINTENANCE SYSTEM REV03...

Page 2: ...REV03016703010220 1...

Page 3: ...rical 11 Field Connections If Applicable 11 Plumbing 11 Typical Plumbing Installation Schematically 12 Important Installation Precautions 12 Multi Tank Installation If Applicable 12 Controller 14 Sett...

Page 4: ...tom Troubleshooting Guide 22 AXI International Limited Warranty 23 Warranty Claim Procedure 24 Technical Assistance and Ordering 25 Accessories and Additional Configuration Parameters 25 Replacement F...

Page 5: ...C Operating Temperature 7000 Series 41 122 F 5 50 C Electrical 120V 60Hz 15A 1Ph or 230V 50Hz 15A 1Ph Pump 1 3 HP Spur Gear Pump Suction Capability Primed 15ft vertical lift or 100ft horizontal run li...

Page 6: ...Water Detection Alarm Module Vacuum Pressure Switches Flow Switch Leak Detection Float Switch Inlet and Outlet Isolation Ball Valves Pump Motor 1 3 HP Gear Pump Primary Filter Water Separator Fuel Fil...

Page 7: ...in Valve Basket Strainer Water Collection Drum o High Water Level Float Switch Manual Additive Injection If Applicable System Ball Valve Additive Injection Port Injection Port Ball Valve Auto Additive...

Page 8: ...ion o Activated when the Vacuum Switch placed on the suction side of the pump set detects a reading above the factory set point The system will go into an alarm state and the pump will not be allowed...

Page 9: ...or operate system without high fuel level alarms from both tanks tied into the control panel Frequently test overflow alarms for proper functionality and pump shutdown Auto Water Drain AWD If Applicab...

Page 10: ...the treatment ratio For example 5 Gallon Jug of AFC treats 25 000 gallons of fuel so enter 1 5000 6 Once this information is entered press the START button to begin the injection process 7 There is a...

Page 11: ...lectrical problems Immediately report or note any damages to the shipper Checklist If the packing crate shows signs of damage inspect the system for damage Check the entire system for damage that coul...

Page 12: ...to the ground studs provided as shown on the provided drawings After the initial wiring of the system check operation to ensure that the motor is running in the correct direction If the motor is runn...

Page 13: ...ed piping size Ref Page 4 Inlet Outlet Port or more with no additional flow restrictions That includes valves 90 degree connectors or other plumbing accessories For continuous optimal performance make...

Page 14: ...vided electrical drawings must be wired to the Normally Closed High Level Alarm Contacts on both tanks to avoid overfilling of either tank and potential spills This is a very important safety feature...

Page 15: ...the arrow key to select the Timer and Press OK 5 Use the arrow keys to select the desired field and press OK to edit 6 Use the left and right arrow keys to select the day days of the week the system...

Page 16: ...IP Address 1 From the Main Menu press the CONFIG button 2 Input 9999 and press the enter key 3 Push IP Config and continue onto the next page 4 Enter the desired values for the PLC IP Address PLC IP...

Page 17: ...m gauge on the input side of the pump The gauge should read no more than 15 HG vacuum maximum under normal conditions Vacuum gauge readings reaching 16 HG indicate excessive debris in the primary filt...

Page 18: ...ssioning section Flow Switch When the flow rate drops below the predetermined set point on the flow switch i e 10 GPM the switch will trigger a signal to shut down the pump If the set point is incorre...

Page 19: ...igh Pressure alarm should be indicated on the System Controller Open the outlet ball valve again Reset the alarm by pushing the Alarm Reset button on the enclosure door panel Water Sensor Jump the Wat...

Page 20: ...hs Servicing the Primary Filter Water Separator Clogged primary filter elements restrict the flow of fuel resulting in the system s vacuum gauge indicating a pressure drop The gauge reads the conditio...

Page 21: ...rn the enclosure door panel selector switch to its original position 9 Check for leaks when re starting and pressurizing the system Note Disposal of fuel associated waste and filters must be in accord...

Page 22: ...icing of Water Separator 1 Keep a fuel waste container under the Manual Drain Port 2 Open the bleed screw on top of the Water Separator to break vacuum 3 Open the AWD Isolation Ball Valve and Manual D...

Page 23: ...ve water in tank 2 Restriction in plumbing on discharge side too high 3 Head on discharge side too high 4 Check valve stuck or defective 5 Outlet ball valve not fully open 6 Discharge line clogged Pum...

Page 24: ...t limited to improper installation or location in a harsh corrosive or saltwater environment 5 Failures resulting from attachments accessory items and parts not sold by AXI International 6 Repairs by...

Page 25: ...purchase model number serial number and a detailed explanation of the problem you are experiencing The Customer Service Representative may at the discretion of AXI International arrange for a Field E...

Page 26: ...eters SYSTEM ALARMS Switches and timer delays Type Default Set point Default Timer delay sec AXi international s part number Vacuumswitch 16 in hg 5 0 aa 0528 Pressure switch 22 psi 0 0 aa 0526 Flowsw...