Axi STS 6003 Instruction, Operating, & Maintenance Manual Download Page 13

 

REV03016704010220 

12 

Use proper quality approved fuel line materials with similar inner diameter (ID) to the inlet/outlet of the system. For 
extended suction side plumbing runs, it is recommended to install oversized pipe, (1/4” to 1/2” increased ID) (Ref.: Page 4 
– Suction Capability). 

 
Note: Flexible plumbing is strongly recommended for system inlet and outlet connections to external plumbing in order to 
avoid issues with thermal expansion, prevent putting any stress on the internal fittings of the system, and enable ease of 
maintenance/installation. 
 

The pick-up tube/line(s) should originate from the lowest point of the tank to ensure all water is removed. Also, it should 
be connected directly to the system’s inlet port (located on the left-hand side of the system) and be kept as short as 
possible. It is recommended that an oversized, low restriction foot valve be installed to keep the system primed, especially 
if the inlet port of the system is located above the lowest possible level of fuel in the tank. Additionally, a priming tee 
should be installed at the highest point of the suction line to enable priming of the pipelines and system.  
 
The return line(s) should be plumbed to the system’s outlet port (located on the right-hand side of the system) and enter 
the tank as far as possible away from the pick-up tube, close to the tank bottom. 
 
Multiple suction and/or return lines may be connected to a manifold outside the system. 
 

Note: Anti-Siphon or other external plumbing devices may be required by state and/or local regulations & code.  

 
Cumulatively, the system capabilities are 15 FT. (4.57 m) suction (vertical lift) or 100 FT. (30.48 m) horizontal run, when 
connected to the minimum recommended piping size (Ref.: Page 4 – Inlet/Outlet Port), or more, with no additional flow 
restrictions. That includes valves, 90-degree connectors, or other plumbing accessories. For continuous optimal 
performance, make sure suction and discharge lines are free of contamination, nothing is blocking the flow of fuel, and the 
suction line always stays primed.  
 

Note: Plumbing installation must be in accordance with all applicable federal, state, and local rules, laws, standards, and 
regulations. 
 
Note: Additionally, if the system must share a fuel oil supply (FOS) line with a generator, we recommend check valves be 
installed after the split in the line, before the landing/entrance into the generator tank and the fuel polishing system. Also, it 
is highly recommended that the “External Shut Down” contacts on the PLC are utilized as well in this scenario.  

Typical Plumbing Installation (Schematically) 

See provided P&ID drawing(s). 

Important Installation Precautions 

The suction line of the system should be independent and separate from the suction line of the engine. If that is not 
possible, appropriate valves must be installed to completely separate the system from the engine’s fuel system to prevent 
any possible interference with safe engine operation (please see note above).  
 
Also, it is highly recommended to plumb the discharge line independent and separate of the engine’s fuel return line back 
to the tank. If the return line from the engine and the discharge of the system must be combined in any way, adequate 
valves should be installed to prevent any possible interference with safe engine operation. 

Multi-Tank Installation – 

If Applicable 

Please connect each tank’s dedicated supply and return lines according to the provided drawings. Use approved flexible 
lines to allow to avoid issues with thermal expansion, prevent putting stress on plumbing connections, and enable ease of 
maintenance/installation. 

Summary of Contents for STS 6003

Page 1: ...Dr Fort Myers FL 33905 239 690 9589 Toll Free 877 425 4239 FAX 239 690 1195 www AXI International com STS STS 6003 7003 Instruction Operating Maintenance Manual ENCLOSED FUEL MAINTENANCE SYSTEM REV03...

Page 2: ...REV03016703010220 1...

Page 3: ...rical 11 Field Connections If Applicable 11 Plumbing 11 Typical Plumbing Installation Schematically 12 Important Installation Precautions 12 Multi Tank Installation If Applicable 12 Controller 14 Sett...

Page 4: ...tom Troubleshooting Guide 22 AXI International Limited Warranty 23 Warranty Claim Procedure 24 Technical Assistance and Ordering 25 Accessories and Additional Configuration Parameters 25 Replacement F...

Page 5: ...C Operating Temperature 7000 Series 41 122 F 5 50 C Electrical 120V 60Hz 15A 1Ph or 230V 50Hz 15A 1Ph Pump 1 3 HP Spur Gear Pump Suction Capability Primed 15ft vertical lift or 100ft horizontal run li...

Page 6: ...Water Detection Alarm Module Vacuum Pressure Switches Flow Switch Leak Detection Float Switch Inlet and Outlet Isolation Ball Valves Pump Motor 1 3 HP Gear Pump Primary Filter Water Separator Fuel Fil...

Page 7: ...in Valve Basket Strainer Water Collection Drum o High Water Level Float Switch Manual Additive Injection If Applicable System Ball Valve Additive Injection Port Injection Port Ball Valve Auto Additive...

Page 8: ...ion o Activated when the Vacuum Switch placed on the suction side of the pump set detects a reading above the factory set point The system will go into an alarm state and the pump will not be allowed...

Page 9: ...or operate system without high fuel level alarms from both tanks tied into the control panel Frequently test overflow alarms for proper functionality and pump shutdown Auto Water Drain AWD If Applicab...

Page 10: ...the treatment ratio For example 5 Gallon Jug of AFC treats 25 000 gallons of fuel so enter 1 5000 6 Once this information is entered press the START button to begin the injection process 7 There is a...

Page 11: ...lectrical problems Immediately report or note any damages to the shipper Checklist If the packing crate shows signs of damage inspect the system for damage Check the entire system for damage that coul...

Page 12: ...to the ground studs provided as shown on the provided drawings After the initial wiring of the system check operation to ensure that the motor is running in the correct direction If the motor is runn...

Page 13: ...ed piping size Ref Page 4 Inlet Outlet Port or more with no additional flow restrictions That includes valves 90 degree connectors or other plumbing accessories For continuous optimal performance make...

Page 14: ...vided electrical drawings must be wired to the Normally Closed High Level Alarm Contacts on both tanks to avoid overfilling of either tank and potential spills This is a very important safety feature...

Page 15: ...the arrow key to select the Timer and Press OK 5 Use the arrow keys to select the desired field and press OK to edit 6 Use the left and right arrow keys to select the day days of the week the system...

Page 16: ...IP Address 1 From the Main Menu press the CONFIG button 2 Input 9999 and press the enter key 3 Push IP Config and continue onto the next page 4 Enter the desired values for the PLC IP Address PLC IP...

Page 17: ...m gauge on the input side of the pump The gauge should read no more than 15 HG vacuum maximum under normal conditions Vacuum gauge readings reaching 16 HG indicate excessive debris in the primary filt...

Page 18: ...ssioning section Flow Switch When the flow rate drops below the predetermined set point on the flow switch i e 10 GPM the switch will trigger a signal to shut down the pump If the set point is incorre...

Page 19: ...igh Pressure alarm should be indicated on the System Controller Open the outlet ball valve again Reset the alarm by pushing the Alarm Reset button on the enclosure door panel Water Sensor Jump the Wat...

Page 20: ...hs Servicing the Primary Filter Water Separator Clogged primary filter elements restrict the flow of fuel resulting in the system s vacuum gauge indicating a pressure drop The gauge reads the conditio...

Page 21: ...rn the enclosure door panel selector switch to its original position 9 Check for leaks when re starting and pressurizing the system Note Disposal of fuel associated waste and filters must be in accord...

Page 22: ...icing of Water Separator 1 Keep a fuel waste container under the Manual Drain Port 2 Open the bleed screw on top of the Water Separator to break vacuum 3 Open the AWD Isolation Ball Valve and Manual D...

Page 23: ...ve water in tank 2 Restriction in plumbing on discharge side too high 3 Head on discharge side too high 4 Check valve stuck or defective 5 Outlet ball valve not fully open 6 Discharge line clogged Pum...

Page 24: ...t limited to improper installation or location in a harsh corrosive or saltwater environment 5 Failures resulting from attachments accessory items and parts not sold by AXI International 6 Repairs by...

Page 25: ...purchase model number serial number and a detailed explanation of the problem you are experiencing The Customer Service Representative may at the discretion of AXI International arrange for a Field E...

Page 26: ...eters SYSTEM ALARMS Switches and timer delays Type Default Set point Default Timer delay sec AXi international s part number Vacuumswitch 16 in hg 5 0 aa 0528 Pressure switch 22 psi 0 0 aa 0526 Flowsw...

Reviews: