System Operation
!WARNING! This system is not meant for use with gasoline or any other flammable liquids having a flash
point less than 100°F (37.8° C). Use with gasoline or any flammable liquids at a temperature exceeding their
flash point presents an immediate explosion and fire hazard.
Pump Operation
Apply power to unit via toggle switch.
Automatic:
Program timer to run. When the timer contacts close, the pump will start and run until the timer setting has expired. See the
Controller section for setting run times.
Manual (Override):
Press manual button. The pump motor will run until the automatic setting is reactivated, or until an alarm or overload has
been tripped.
Filter Configurations
The AXI in-line filtration setup allows for various modes of operation. A filter can be installed to clean particulate, or both
water and particulate, out of the flow stream of fuel.
Note: For optimal performance and water block filter life, bulk free water should be removed before using an SFM Series
system.
Alarms
The SFM 1080 is equipped with an AXI International SMART Solar Controller. Alarm status are displayed on the industrial
control panel (on the door) via indicator lights.
Alarms featured on the SFM 1080 include:
•
Leak Detection (system shutdown)
•
High vacuum (system shutdown via vacuum switch)
• Pump high pressure (system shutdown via
pressure switch)
Once triggered alarms are addressed, each alarm can be reset by pressing the reset push button located on front of the
controller.