AWG I Operating manual I Fittings I
Inductors FD Z2 and Z4
USE
M1088B10 I Rev. 01-02/20
ENGLISH
35 / 40
5.3
Visual inspection after each use
The inductor is separated from the water supply.
The inductor must not be contaminated with foam agent. If neces-
sary, rinse the inductor again as described in the previous section.
1. Check the inductor and the pick tube (accessory) for visible damage.
Important
Do not continue to use damaged components!
If you discover any damage, this must be reported to
the person or department responsible.
6
FUNCTIONAL TEST
6.1 Prerequisites
All testing of the AWG Inductors FD Z2 and Z4 must be carried out in
accordance with the manufacturer's technical documentation and must
be documented if necessary.
The following inspections are defined for the inductors:
– Mandatory BASIC Inspection after each use
– Mandatory STANDARD Inspection every 12 months
– Optional ADVANCED Inspection every 12 months
The STANDARD and ADVANCED inspections may only be carried out
by qualified personnel who have been trained for these inspections:
– Firefighters who have received training as firefighting equipment
maintenance technicians or persons with equivalent qualifications
– or, if desired, directly by the manufacturer
Inspection by the manufacturer
AWG Fitting GmbH offers an inspection as part of its service offering.
Send us your inductor and you will receive the inspected device back
by the agreed date. You will find a return delivery form on our website
www.awg-fittings.com. If required, a rental device can also be provided.