Relay Switch Sensor (RMA-RELAY-SEN)

Step 3: Connect a low-voltage device to your Relay Switch.

Disconnect power to the electrical device before beginning.

Do not connect the relay outputs on AVTECH products to live circuits of over 125VAC or 

24VDC.

Use an appropriate wire to connect the relay ports to your electrical device; consult an 

electrician if you are unsure if the wire is compatible with the electrical load or device.

Use an appropriate wire or cable to connect the relay ports to your electrical device. If 

you are unsure if the wire is compatible with the electrical load or device, contact an 

electrician.

1.  Separate and strip the free ends of the wire. Expose about ¼" of 

wire.

2.  Connect one end of the wire to an output port on the Relay 

Switch. The port’s contacts are non-polarized, so you may insert 

either side of the wire into either contact.

3.  Connect the other end to the appropriate contacts on your electrical device.

4.  Repeat this procedure for up to 3 more electrical devices.

Sensor Features & Specifications

Environment Condition Monitored

Turns on/off low-voltage electrical devices

Type Of Sensor

Relay output

Power Supply

Room Alert or Light Tower Adapter (LTA)

Sensor Cable Type

Relay output cable

Included

No

Maximum Extendible Length

Depends on application/type

Custom cable

Included

Yes (built-in)

Length

3' 11"

Maximum Extendible Length

900'

Operating Temperature

-40º F to 185º F (-40º C to 85º C)

Maximum Load On Relay Ports

0.3A at 125VAC; 1A at 24VDC

Compatible Products

     Adapter

Light Tower & Relay Adapter (LTA)

     Main Units

Room Alert 32E/W, 12E and 3E (LTA required)

Room Alert 4E (no LTA required)