- 12 -
IST0649V1/0
ALLARME
NO
NC
+F
GUASTO
C
NO
NC
C
OUT
+ -
B
A
R1
CONNECTIONS TO CONTROL UNITS
BF100R beam is equipped with:
ALLARME
NO
NC
+F
GUASTO
C
NO
NC
C
OUT
R1
R2
In both cases, if module BR100 is used, reset can be done through mechanical key on board.
-
Relay ALARM output.
Contacts of this output can be C/NC or C/
NO according to setting of jumper S7 (see
chapter JUMPER).
In order to reset the beam from alarm
condition, it is necessary to take off supplying
from the beam for a few seconds (Jumper
S9 open).
An example of connection using these contacts is
shown on side-drawing where ALARM contact is
set on C/NO and FAULT relay is set on C/NC.
R1 is the end-line resistence which is usually given
within control unit.
R2 is the alarm resistence (for AVS control units
the value of this resistence is 680/1000 ohm –
3W) (not included).
-
OUT + F for direct connection to
AVS conventional fire control units
(charge of 680 ohm during alarm).
In order to reset the beam from
alarm condition, simply make a
reset operation on control unit
(Jumper S9 closed).
Side-drawing shows an example
of connection using these
contacts: R1 is the end-line
resistance usually given with
control unit. FAULT contact is set
on C/NC.
Summary of Contents for BF100 A
Page 13: ...13 IST0649V1 0...
Page 14: ...14 IST0649V1 0...