background image

Specifications

66

Avaya Model 6000 UPS Operator’s Manual

S

167-405-115 Issue 5

Uncontrolled Copy

Summary of Contents for 4500 VA

Page 1: ...Site Preparation Installation and Operator s Manual for Avaya Avaya Series 1 Uninterruptible Power Systems Models 4500 5000 6000 VA Select Code 167 405 115 ...

Page 2: ...ction against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the us...

Page 3: ...e Preparation Installation and Operator s Manual for Avaya Avaya Series 1 Uninterruptible Power Systems Models 4500 5000 6000 VA Select Code 167 405 115 Issue 5 Copyright 2001 Avaya Inc All Rights Reserved ...

Page 4: ... the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information INPUT BREAKER Indicates the input breaker which shuts off utility power to the PPU BATTERY BREAKER Indicates the battery breaker which shuts off battery power power transmission through the battery cord when in the OFF O position BATTERY CONNECTOR Indicates the b...

Page 5: ...ION CAUTION Read the safety instructions beginning on page 5 before installing the UPS 1 Desired Output Voltage Voltage Selector Position 100 200V 200 110 220V 220 115 230V 230 120 240V 208 if UPS Input is 208V 240 if UPS Input is 240V ...

Page 6: ...UPS with BDM Quick Installation 5 6 7 8 9 ...

Page 7: ...Installation Notes Read Before Installing the UPS 23 Systems That Require Contact Closure 24 Systems That Require a Serial Interface 24 Installing the UPS 24 REPO Installation 35 UPS with BDM Startup 37 Troubleshooting Tips 39 EPDM Configurations 40 4 UPS Operation 41 UPS Front Panel 41 Operating Modes 42 Normal Mode 42 Bypass Mode 43 Battery Mode 43 Diagnostics 44 Battery Test on Demand 44 Batter...

Page 8: ...2 UPS Serial Communications Menu 54 UPS Communications Interface Port 57 Communications Mode Reference Chart 59 6 Specifications 61 Model 6000 Specifications 61 UPS Physical Specifications 62 UPS Technical Specifications 63 Electrical Specifications for the Model 6000 with BDM 64 7 Troubleshooting 67 Resetting the UPS 69 Silencing the Alarm 69 Service and Support 69 Parts List 70 Index 71 ...

Page 9: ...ble power Voltage spikes power surges brownouts and power failures have the potential to corrupt critical data destroy unsaved work sessions and in some instances damage expensive hardware Now you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment The Bypass Distribution Module BDM has a Maintenance Bypass feature that supplies po...

Page 10: ...Introduction 2 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy Figure 1 Model 6000 UPS ...

Page 11: ...load in volt amperes VA The total load VA should not exceed the UPS VA rating To determine the total load requirements 1 Obtain the load ratings from either the nameplate or operator s manual of the equipment to be protected by the UPS The ratings are listed in either watts W amperes or amperes max A or volt amperes VA 2 If the rating is in watts multiply by 1 4 to obtain the VA requirement this i...

Page 12: ...mber of pieces of equipment or use a UPS with a larger load capacity When deciding on which pieces of equipment to remove from the UPS select equipment that has a lower priority for power protection Computers monitors and modems typically have a higher priority because they could be processing or transmitting data when a power outage occurs NOTE DO NOT protect laser printers with the UPS because o...

Page 13: ...energy source batteries The output receptacles may carry live voltage even when the UPS is not connected to an AC supply S Never dispose of batteries in a fire Batteries may explode when exposed to flame S Never open or mutilate batteries Released electrolyte is harmful to the skin and eyes and may be extremely toxic S To reduce the risk of fire or electric shock install this UPS in a temperature ...

Page 14: ...ioner og vedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER Ingen af UPS ens indvendige dele kan repareres af brugeren ADVARSEL S Batterier kan udgøre en fare for elektrisk stød eller forbrændinger forårsaget af høj kortslutningsspænding De korrekte forholdsregler bør overholdes S Korrekt bortskaffelse af batterier er påkrævet Overhold gældende lokale regler for bortskaffelsesproced...

Page 15: ...udgange skal overstrømsbeskyttelsen for AC kredsen e komme andetsteds fra S Med hensyn til Bypass systemer med direkte forbundne udgange skal afbryderkontakter tilAC kredsløbet med passende mærkeeffekt kommeandetsteds fra Belangrijke Veiligheidsinstructies BELANGRIJKE VEILIGHEIDSINSTRUCTIES BEWAAR DEZE INSTRUCTIES DEZE HANDLEIDING BEVAT BELANGRIJKE VEILIGHEIDSINSTRUCTIES GEVAAR Deze UPS bevat LEVE...

Page 16: ...ebeveiliging meer hebben S De hoofdvoedingcontactdoos moet zich op minder dan 2 meter van de apparatuur bevinden en makkelijk bereikbaar zijn voor de gebruiker De aan uit schakelaar op de UPS biedt geen elektrische isolatie voor de inwendige onderdelen De stekker uit de voedingcontactdoos halen wanneer het apparaat voor lange tijd niet wordt gebruikt S Neem er nota van dat de uitgangaansluit punte...

Page 17: ...ektrolyytti on vahingollinen iholle ja silmille ja voi olla erittäin myrkyllistä S Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia Ympäristön lämpötila ei saa ylittää 40 C Älä käytä lähellä vettä ja vältä kosteita tiloja 95 maksimi S Älä poista tai irrota sisääntulojohtoa kun UPS o...

Page 18: ...autions nécessaires S Une mise au rebut réglementaire des batteries est obligatoire Consulter les règlements en vigueur dans votre localité S Cet onduleur renferme sa propre source d énergie batteries Les prises de sortie peuvent être sous tension même lorsque l onduleur n est pas branché sur le secteur S Ne jamais jeter les batteries au feu L exposition aux flammes risque de les faire exploser S ...

Page 19: ...urant alternatif est à se procurer auprès d un autre fournisseur S Pour les systèmes de bypass dotés de sortie à bornier les interrupteurs adaptés au circuit de courant alternatif sont à se procurer auprès d un autre fournisseur Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGENANLEITUNGEN AUFBEWAHREN DIESES HANDBUCH ENTHÄLT WICHTIGE SICHERHEITSANWEISUNGEN WARNUNG Die USV führt lebensgefährliche...

Page 20: ...wird S Die Netzsteckdose die zur Hauptversorgung verwendet wird darf sich nicht weiter als 2 Meter vom Gerät weg befinden und muß für den Bediener erreichbar sein Der Ein Aus Schalter der USV bietet keine elektrische Isolation der internen Teile Wenn das Gerät längere Zeit nicht benutzt wird sollte es von der Netzsteckdose abgezogen werden S Beachten daß die Ausgangssteckdosen auf der USV jedesmal...

Page 21: ...00 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy S 0 1 2 3 4 5 36 6 7 60 S 8 69 4 2 2 7 2 8 69 S 8 8 0 8 6 8 8 8 2 S 6 7 6 2 S 7 2 9 9 9 3 63 8 6 0 6 0 S 4 8 6 0 4 9 4 6 9 36 8 0 6 A 6 3 B CDE S 3 6F F 48 7 8 7 7 0 8 8 ...

Page 22: ...SICUREZZA PERICOLO La TENSIONE contenuta in questo gruppo statico di continuità è LETALE Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO All interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL UTENTE ATTENZIONE S Le batterie possono presentare rischio di scossa elettrica o di ustioni provocate da a...

Page 23: ...to a terra di sicurezza del gruppo statico di continuità e dell apparecchiatura ad esso collegata S La presa di alimentazione principale non deve trovarsi a oltre 2 metri dall apparecchiatura e deve essere accessibile all operatore L interruttore on off del gruppo statico di continuità non isola elettricamente i componenti interni Scollegare l unità dalla presa di alimentazione quando rimane in ri...

Page 24: ...r denne UPS en installeres i et innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende forurensende stoffer Romtemperaturen må ikke overskride 40 C Den må ikke brukes i nærheten av vann eller ved meget høy luftfuktighet 95 maks S Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS en er på slik at ikke sikkerhetsjordingen fjernes fra UPS en og det utstyret...

Page 25: ...e as baterias no fogo porque há risco de explosão S Nunca abra ou danifique as baterias O eletrólito liberado é prejudicial à pele e aos olhos e pode ser extremamente tóxico S Para reduzir o risco de incêndios ou choques elétricos instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condutíveis A temperatura ambiente não deve exceder 40_C Não opere pró...

Page 26: ... Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ Внутри ИБП нет узлов ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ ОСТОРОЖНО S Аккумуляторы могут вызвать опасность поражения электрическим током или ожога от тока короткого замыкания Соблюдайте соответствующие меры предосторожности S Необходимо соблюдать правила утилизации аккумуляторов Обратитесь к местным норм...

Page 27: ...тупной для оператора Выключатель ИБП не отключает внутренние узлы от входного электропитания При отключении оборудования на продолжительные интервалы времени отсоедините входной сетевой шнур от настенной розетки S Пожалуйста обратите внимание на то что выходные розетки ИБП находятся под электрическим напряжением если была нажата кнопка включения выхода ИБП даже если входной сетевой шнур отключен S...

Page 28: ...tir corriente eléctrica aun cuando el SIE no esté conectado a un suministro de corriente alterna c a S Nunca deseche las baterías en el fuego Las baterías pueden explotar si se las expone a la llama S Nunca abra ni dañe las baterías El electrolito que se libera es perjudicial para la piel y los ojos y puede ser extremadamente tóxico S Para reducir el riesgo de incendio o de choque eléctrico instal...

Page 29: ...ENNA BRUKSANVISNING INNEHÅLLER VIKTIGA SÄKERHETSFÖRESKRIFTER FARA Denna UPS enhet innehåller LIVSFARLIG SPÄNNING ENDAST AUKTORISERAD SERVICEPERSONAL får utföra reparationer eller service Det finns inga delar som ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS enheten VIKTIGT S Batterierna kan ge elektriska stötar eller brännskador från hög kortslutningsström Följ tillämpliga anvisningar S Batterierna m...

Page 30: ...dden dras ur vägguttaget S Observera att UPS enhetens uttag är strömförande när laddningsström brytaren Output On button trycks ned oberoende av om spänningskällan är tillkopplad eller inte S Minska brandrisken genom att ansluta UPS enheten och förbikopplings modulen till kretsar som försetts med överströmsskydd i form av en avgreningskoppling på max 30 ampere S Överströmsskydd för de utgående väx...

Page 31: ...rior to use store them in a cool dry environment Storage temperature should not exceed 35 C 95 F in order to preserve battery life For longer term storage energize the power processing unit and battery module for approximately 8 hours every 90 days in order to maintain battery charge Whenever the units are not energized verify the circuit breaker on all battery modules is returned to the OFF O pos...

Page 32: ...open when the alarm is not present and closed when an alarm occurs 2 Connect the alarm adapter to the unit s RS 232 port and the modular output to the computer wallfield etc through an 8 pin modular plug Comcode PEC For 3B2 systems use 406707737 24024 For all other systems use 407691401 24433 Systems That Require a Serial Interface 1 For installations that require a serial interface set the system...

Page 33: ... s Manual S 167 405 115 Issue 5 Uncontrolled Copy 1 4 20 x 1 2 Screws Stacking Module Cover the smaller flanges without holes face toward the front Battery Modules PPU BDM 1 4 20 x 1 2 Screws Caster Base Floor Mounting Plate Figure 3 UPS with BDM ...

Page 34: ... mounting plate complete Steps A and B This plate is required only for seismic applications but can also be used to prevent rolling or tipping of the assembled rack A F F F Fo o o or r r r S S S Se e e ei ii is s s sm m m mi ii ic c c c I I I In n n ns s s st t t ta a a al ll ll ll la a a at t t ti ii io o o on n n n Prepare the floor by referring to the hole pattern shown below The mounting plate...

Page 35: ...ogether on the side with two of the 1 4 20 x 1 2 screws provided 4 Slide the cover over the stacked modules and secure with four of the 1 4 20 x 1 2 screws provided Tighten the screws until the cover s flanges are pulled flat against the caster base 5 If more than two batteries are to be used place the batteries in another Stacking Module Separate battery stacks must go to the left of the Stacking...

Page 36: ...uit Breaker Battery Module Battery Module Battery Connector Voltage Selector Switch REPO Receptacle Battery Connector Guard Serial Port PPU Battery Connector Breaker Tie Input Plug Input Breaker Output Receptacle 568 mm 22 35I 252 mm 9 91I Depth of Unit 406 mm 16I Figure 4 UPS with Battery Modules Rear View ...

Page 37: ...nput Voltage Selector Switch Figure 5 BDM Plug Receptacle Unit Rear Panel Connections 9 Select the correct UPS output voltage according to the BDM model BDM Model Number UPS Voltage Selector Switch Position 208 120 240 Hardwired Set to 208V for 120 240V BDM output Set to 220V for 127 220V BDM output 60 Hz units only 208 240 120 L5 30R 208 or 240 208 240 120 240 L14 30R 208 or 240 240 120 240 Hardw...

Page 38: ...0 Turn the BDM input voltage selector switch to 208 or 240 according to the UPS input voltage see Figure 5 or Figure 7 11 If your BDM is a plug receptacle unit complete Steps 12 and 13 If you need to hardwire the BDM skip to Step 15 12 Plug the input and output power cords of the BDM into the input and output power connectors located on the PPU rear panel see Figure 4 and Figure 5 Figure 19 on pag...

Page 39: ...cian should perform the hardwired installation Input Conduit Entry Output Conduit Entry Bypass Switch Input Breaker Input Cable Connections TB1 Output Cable Connections TB2 BDM Input Voltage Selector Switch Figure 7 Hardwired BDM with rear panel cover removed 16 Hardwire the input TB1 and output terminations TB2 for the BDM See the following hardwired terminations table for specifications See Figu...

Page 40: ...34 93 mm ollowing Output Wiring Table TB2 1 6 18 AWG 16 0 mm2 8 AWG 10 mm2 access hole for 1I 25 4 mm Neutral TB2 4 16 0 mm2 10 mm2 1I 25 4 mm conduit Ground TB2 5 Use 75 C copper wire Suggested wire size is based on Model 240 120 240 hardwire full load ratings applied to NEC Code Table 310 16 BDM Hardwired Models Output Wiring Model 240 120 240 Model 240 120 240E Output Voltage Terminal Position ...

Page 41: ... and 3 However the voltage available between 4 and 1 is only 88 Vac NOT 120 Vac Therefore unless special requirements exist for 208 Vac 120 240 Vac should be wired to the customer provided distribution panel Figure 8 Hardwired Output Connections TB1 Input Connection Output Connection TB2 Neutral Bonding Jumper TB2 1 TB2 2 TB2 3 Neutral Ground Line 1 Ground Line 2 Neutral Figure 9 Hardwired BDM Ter...

Page 42: ... to the grounded and ungrounded branch circuit supply conductors S Color consult local code requirements for ground wire color code usually green with or without a yellow stripe S Ground should be grounded to the earth ground in the service equipment or in the supply transformer if supplied by a separately derived system NOTE All attachment plug receptacles on or connected to the UPS or system equ...

Page 43: ... S Minimum ratings of 240 Vac and 35 mA S Wire should be 18 AWG 0 75 mm2 minimum CAUTION The black and white REPO wires are at high voltage potential 240V Refer to your local electrical code for proper installation of the high voltage REPO wires The optional three wire REPO cord see Figure 10 can be ordered from the manufacturer The green wire is a safety ground for the REPO conduit The REPO funct...

Page 44: ...e using the optional REPO cord junction box place the conduit through the access hole on the junction box Connect the exposed conduit wires to the corresponding compression terminals see the following table Tighten the compression terminals with a screwdriver see Figure 11 Mounting Holes Plug Receptacle PPU Connector Three Foot Cord Terminal Block Access Hole for Conduit Figure 11 Optional REPO Co...

Page 45: ...ted see Step 9 on page 29 3 Turn on the equipment that is connected to the UPS 4 Verify that the Bypass switch on the BDM rear panel is in the NORMAL position see Figure 5 on page 29 5 If your BDM is hardwired supply utility power to the UPS skip to Step 8 6 If your BDM is a plug receptacle unit plug the input power supply cord into the utility input receptacle on the BDM rear panel 7 Plug the oth...

Page 46: ...iagnostic tests and enters Normal mode with the equipment load offline The µindicator remains lit The startup should take about 15 seconds 12 Press and hold the Output On button until you hear the UPS beep approximately one second The µindicator remains lit and the Self Test indicator turns on The front panel displays the percentage of full load being applied to the UPS The UPS is now in Normal mo...

Page 47: ...y module s charged However batteries may lose some of the charge during shipping and storage You can use the UPS immediately after unpacking but it may not provide the full rated backup time during a power failure Upon initial startup operate the UPS for approximately 8 hours to ensure the battery is fully charged and full backup time is available If the I3 indicator flashes operate the UPS for 24...

Page 48: ... 405 115 Issue 5 Uncontrolled Copy EPDM Configurations PDM01 PEC 24450 PDM02 PEC 24450 PDM03 PEC 24450 L14 30P Input Cord L14 30P Input Cord L14 30P Input Cord PDM04 PEC 24450 PDM05 PEC 24451 PDM06 PEC 24451 L14 30P Input Cord L5 30P Input Cord L5 30P Input Cord ...

Page 49: ...s present during operation the indicators flash S Displays the loading percentage during Normal mode and the battery capacity during Battery mode You can also use the front panel to configure UPS communication options See Front Panel Communications Access on page 52 OUTPUT OFF OUTPUT ON ALARM SILENCE Overload Indicator Unlit Amber Green Flashing Indicator Legend Input On Indicator ᎼLoad or Battery...

Page 50: ...ceptacle or Terminal Block Output EMI RFI Filters Surge Suppression EMI RFI Filters Battery Charger Battery Battery Inverter Bypass Line Battery Modules Emergency Power Off Receptacle or Terminal Block Utility Power Rectifier Figure 14 UPS Block Diagram Normal Mode During Normal mode the µindicator illuminates and the front panel displays the percentage of UPS load capacity being used by the prote...

Page 51: ...nd then once every 10 seconds while in Battery mode The indicator illuminates The front panel displays the approximate percentage of battery capacity remaining see Figure 17 When the utility power returns the UPS switches to Normal mode operation while the battery recharges BATTERY ONLINE 75 CAPACITY REMAINS BATTERY ONLINE 50 CAPACITY REMAINS BATTERY ONLINE 25 CAPACITY REMAINS BATTERY ONLINE BATTE...

Page 52: ...ture Test The UPS also runs a series of over 20 internal tests when power is first applied If a diagnostic test fails see Chapter 7 Troubleshooting on page 67 Battery Test on Demand You can perform a battery test on the UPS while it is operating in Normal mode by pressing the Output On button The UPS automatically distributes some of the load to the batteries for 30 seconds and tests the battery s...

Page 53: ...proximately three seconds The µindicator remains lit indicating Normal mode load offline 2 Switch the input breaker on the power processing unit to the OFF O position The UPS enters Battery mode for several seconds The µindicator turns off and the UPS shuts down 3 Unplug or remove utility power from the UPS 4 When all LEDs are no longer illuminated on the UPS switch the circuit breaker to the OFF ...

Page 54: ... Using Maintenance Bypass Use the following procedure to transfer the critical load to Maintenance Bypass AC Line operation and remove the PPU 1 Turn the Bypass switch on the BDM to the BYPASS position see Figure 19 The BDM is now powering your equipment from utility power 2 Press and hold the Output Off button until the long beep ceases approximately three seconds The µindicator remains lit 3 Swi...

Page 55: ...ectors for Locking Receptacles Model Dependent Power Cords to PPU Voltage Selector Switch REPO Receptacle Serial Port Power Processor Input Plug Power Processor Input Breaker Output Receptacle PPU Battery Connector L5 30R or L14 30R Receptacles Model Dependent 5 15R Circuit Protectors BDM Utility Input Receptacle Cord Provided BDM Input Breaker Bypass Switch 5 15R Receptacles BDM Input Voltage Sel...

Page 56: ...8V for 120 240V BDM output Set to 220V for 127 220V BDM output 60 Hz units only 208 240 120 L5 30R 208 or 240 208 240 120 240 L14 30R 208 or 240 240 120 240 Hardwired 240 240 120 240E Hardwired Set to 200V for 100 200V BDM output Set to 220V for 110 220V BDM output Set to 230V for 115 230V BDM output Set to 240V for 120 240V BDM output The UPS output voltage must match input voltage Using a screwd...

Page 57: ... a short delay approximately three seconds the UPS front panel indicators turn on and cycle through several times The µand indicators remain lit for several seconds UPS in Bypass mode 6 Press and hold the Output On button until you hear the UPS beep approximately one second The µindicator remains lit and the Output On indicator turns on 7 Turn the Bypass switch on the BDM to the NORMAL position Th...

Page 58: ...UPS Operation 50 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...

Page 59: ... Mode Printer Mode 2400 Baud with Novell Contacts Printer Mode 19200 Baud with Novell Contacts S LAN Configuration Novell Style Network Interface 3Com Style Network Interface AS 400 Style Network Interface default Custom User Configurable Interface Initial Communications Settings The UPS is factory configured for AS 400 style LAN contacts To verify the initial UPS communications configuration you ...

Page 60: ... ll le e e e L L L LA A A AN N N N C C C Co o o on n n nt t t ta a a ac c c ct t t ts s s s Any baud rate other than 2400 or 19200 with Printer mode or not Printer mode A A A AS S S S 4 4 4 40 0 0 00 0 0 0 S S S St t t ty y y yl ll le e e e L L L LA A A AN N N N C C C Co o o on n n nt t t ta a a ac c c ct t t ts s s s N N N No o o o S S S Se e e er r r ri ii ia a a al ll l Default Select this mode...

Page 61: ...All indicators begin flashing 3 Press and hold the Output Off button a second time until the alarm beeps again A single indicator corresponding with the current setting remains flashing 4 Press the Output Off button to scroll through the communication options top to bottom Each time you press the button the UPS beeps and the next indicator flashes NOTE If you do not save a selection within 30 seco...

Page 62: ...our terminal or operating system documentation for details on configuring the terminal communication settings 3 At the terminal prompt press Control C until the UPS Serial Communications Menu appears UPS SERIAL COMMUNICATIONS MENU SELECT OPERATION MODE ENTER SELECTION 1 CONTINUOUS DUMP 2 3 A B P L Z Q S POLLED DUMP SMART DUMP ASCII TERMINAL VT100 TERMINAL PRINTER DUMP LAN CONFIGURATION SET BAUD RA...

Page 63: ...when using this mode 2 Polled Dump Status information is transmitted only when requested by a poll character Control E 3 Smart Dump Status information is transmitted when polled as in the previous mode However the transmission also occurs automatically whenever UPS status changes For example if there is a power outage UPS status information changes and is therefore automatically transmitted A ASCI...

Page 64: ...tes for configuring LAN communications A Inverter shutdown control is enabled active HIGH 12V SELECT CUSTOM LAN CONFIGURATION ENTER SELECTION B C Q TO QUIT THIS MENU Inverter shutdown control is enabled active LOW 12V Inverter shutdown control is disabled Instructions Choose the desired inverter shutdown function Warning It is recommended that this feature should not be used with normal RS 232 com...

Page 65: ... communications equipment you are using In particular new baud rate selections for the UPS must match your communications equipment UPS Communications Interface Port In addition to configuring the UPS for specific communication options you must also ensure proper use of the serial port when connecting the UPS to your network or monitoring equipment NOTE Semiconductor switch contacts are rated at a...

Page 66: ...t work correctly Consult your network software or server manuals for system shutdown pin assignments The UPS serial port complies with EIA RS 232 standards RS 232 specifies a maximum cable length of 50 feet 15m See Figure 22 for the location of the serial port UPS Rear Panel Serial Port Detail Serial Port Figure 22 Serial Port Location ...

Page 67: ...a from UPS RS232 RxD 3 N A Signal Ground 7 Novell Battery On ON AC 14 16 Open Low Battery TWO MIN 23 24 Closed Signal Ground 7 15 25 Novell Battery On ON AC 14 16 Closed Low Battery TWO MIN 23 24 Closed Signal Ground 7 15 25 3Com Shutdown Remote SHUT DOWN 2 Positive Voltage Low Battery LOW BATT 9 Positive Voltage Battery On PWR FAIL 10 Positive Voltage Signal Ground 7 AS 400 A D f l UPS Available ...

Page 68: ...Communication 60 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...

Page 69: ...utput VA Output Voltage Output Watts Input Current Output Current Normal BTUs hr On Battery BTUs hr 5000 200 3350 19 6A 25 0A 1600 2200 5200 208 3500 19 7A 25 0A 1600 2300 5500 220 3700 19 7A 25 0A 1700 2400 5750 230 3850 19 6A 25 0A 1800 2500 6000 240 4000 19 5A 25 0A 1900 2600 Model 5000 6000 UPS with BDM Nominal Operating Specifications Output VA PPU Output Voltage PPU Output Watts Normal BTUs ...

Page 70: ...9 0A 1400 1900 Model 4500 with BDM Nominal Operating Specifications Output VA PPU Output Voltage PPU Output Watts Normal BTUs hr On Battery BTUs hr 3750 200 2275 1900 2400 3900 208 2375 2000 2400 4125 220 2525 2000 2500 4300 230 2675 2100 2600 4500 240 2775 2200 2700 UPS Physical Specifications Parameter PPU Battery Module Bypass Distribution Module Height 283 mm 11 13I 142 5 mm 5 61I 283 mm 11 13...

Page 71: ...ne wave Output Voltage 200 208 220 230 240 Vac 3 Common Mode Noise Rejection 60 dB 100 kHz Transverse Mode Noise Rejection 80 dB 100 kHz Input Cord Detachable 2 meter cord Outlets One L6 30R Batteries 10 per module 12 Vdc 5 Ah maintenance free rechargeable lead acid Battery Module Voltage 120 Vdc Operating Environment Temperature 10 C to 40 C 50 F to 104 F Humidity 5 to 95 noncondensing Agency App...

Page 72: ...0A 6000 VA 208 240 120 L5 30R 208 Vac 24A 120 Vac 43 3A 5200 VA 208 240 120 L5 30R 200 240 Vac 24A 100 120 Vac 48 3A 5800 VA 208 120 208 L6 20R 208 Vac 24A 120 208 Vac 15 0 20 0A 5200 VA 208 120 208 L6 30R 208 Vac 24A 120 208 Vac 15 0 25 0A 5200 VA 208 240 120 240 L14 30R 208 Vac 24A 120 240 Vac 15 0 21 1A 5000 VA 208 240 120 240 L14 30R 200 240 Vac 24A 100 120 200 240 Vac 15 0 24 7A 5800 VA 240 1...

Page 73: ...08 Vac 15 0 20 0A 3900 VA 208 120 208 L6 30R 208 Vac 24A 120 208 Vac 15 0 25 0A 3900 VA 208 240 120 240 L14 30R 208 Vac 24A 120 240 Vac 15 0 21 1A 3900 VA 208 240 120 240 L14 30R 200 240 Vac 24A 100 120 200 240 Vac 15 0 24 7A 4500 VA 120V 4500 VA 240V 240 120 240E Hardwired 200 240 Vac 24A 100 120 200 240 Vac 30 0 25 0A European IT Neutral 4500 VA 120V 4500 VA 240V 240 120 240 L6 20R 200 240 Vac 2...

Page 74: ...Specifications 66 Avaya Model 6000 UPS Operator s Manual S 167 405 115 Issue 5 Uncontrolled Copy ...

Page 75: ... beeps occasionally Normal operation None UPS is protecting your equipment indicator remains lit even though line voltage is Utility line is out of specification Test wall socket repair as required even though line voltage is present UPS input breaker is tripped Reduce load then reset breaker UPS does not provide the expected backup time Battery circuit breakers are in the OFF O position Switch th...

Page 76: ...overload increased above 105 The alarm beeps Reduce load If the Overload indicator remains lit reset the UPS by pressing the Output On button until the alarm beeps You may need to obtain a larger capacity UPS OVERLOAD I1 I2 I3 OUTPUT ON The utility line voltage and frequency are out of specification The inverter remains online deriving power from the utility until it is no longer acceptable Check ...

Page 77: ... Retest Have batteries replaced if condition persists Resetting the UPS To reset the UPS while an alarm condition is present press the Output On button until the UPS alarm beeps Silencing the Alarm To silence the alarm for an existing fault press and hold the Output On button for one second The alarm becomes quiet If UPS status changes the alarm beeps overriding previous alarm silencing Press the ...

Page 78: ...cking Module 3 High 407483270 Stacking Module Spacer Cabinet 407483320 4500 5000 6000 Battery Module 407464254 5 Ah Battery Module 1 String REPO Cord 407464288 Remote Emergency Power Off Cord EBC 120 Vdc 4500 5000 6000 407483346 Extended Battery Cabinet PDM01 407465889 Cord connected EPDM L14 30P with 4 5 15R2s PDM02 407465913 Cord connected EPDM L14 30P with 2 5 15R2s and 2 L14 30Rs PDM03 4074833...

Page 79: ...put connector 28 output connector 28 storage 23 Battery Fault alarm 68 Battery Mode 43 Battery Start 44 Battery Test on Demand 44 baud rates 54 57 Bypass Distribution Module BDM AC Line operation 46 block diagram 46 changing BDM input voltage 30 changing output voltage 48 hardwired input and output connections 31 installation 24 Maintenance Bypass feature 24 operation 46 plug receptacle power outp...

Page 80: ...tions 41 indicators 41 front panel configuration 3Com 52 AS 400 52 Novell 52 printer mode 52 H hardwired BDM Bypass switch 31 input and output terminations 32 input breaker 31 input cable connections 31 output cable connections 31 output wiring 32 termination blocks 33 I indicators front panel 41 input cord 37 63 Input On Indicator 41 input voltage selector switch 29 Inverter Shutdown Control 56 L...

Page 81: ...PS with BDM 46 Output Off Button 41 Output On Button 41 Output On Indicator 41 Output Voltage Selector Switch 28 changing 45 Overload condition 68 Indicator 41 Overtemperature alarm 68 P plug receptacle PPU external battery connector 28 input breaker 28 installation optional REPO cord junction box 36 REPO cord 35 REPO switch 35 power input connector 28 power output receptacles 28 rear panel 28 REP...

Page 82: ...sts 44 storage temperature 23 Switch BDM Input Voltage Selector 29 Bypass 29 31 Output Voltage Selector 30 system requirements 3 T Terminal Modes 55 Tests Battery on demand 44 diagnostic 44 troubleshooting chart 67 tips 39 U uninterruptible power system 1 UPS alarm silencing 69 alarms 68 block diagram 42 changing output voltage 45 communication 51 Communications Mode Reference Chart 59 front panel...

Page 83: ......