UPS Operation
49
Avaya Model 6000 UPS Operator’s Manual
S
167-405-115 Issue 5
Uncontrolled Copy
Voltage
Selector
Switch
Figure 20. Voltage Selector Switch
4.
Plug the input and output cords of the BDM into the power
connectors on the PPU as shown in Figure 19 on page 47.
5.
Switch the PPU input breaker to the ON (
|
) position.
After a short delay (approximately three seconds), the UPS
front panel indicators turn on and cycle through several times.
The
µ
and
indicators remain lit for several seconds (UPS
in Bypass mode).
6.
Press and hold the Output On button until you hear the UPS
beep (approximately one second).
The
µ
indicator remains lit and the Output On indicator
turns on.
7.
Turn the Bypass switch on the BDM to the NORMAL position.
The front panel displays the percentage of full load being
applied to the UPS. The UPS is now in Normal mode with the
load online.