Specifications
62
Avaya Model 6000 UPS Operator’s Manual
S
167-405-115 Issue 5
Uncontrolled Copy
Model 4500 UPS (Nominal Operating Specifications)
Output VA
Output
Voltage
Output
Watts
Input Current
Output Current
Normal
(BTUs/hr)
On Battery
(BTUs/hr)
3750
200
2500
14.6A
19.0A
< 1200
< 1600
3900
208
2600
14.6A
19.0A
< 1200
< 1700
4125
220
2750
14.6A
19.0A
< 1300
< 1800
4300
230
2900
14.6A
19.0A
< 1400
< 1900
4500
240
3000
14.6A
19.0A
< 1400
< 1900
Model 4500 with BDM (Nominal Operating Specifications)
Output VA
(PPU)
Output Voltage
(PPU)
Output Watts
Normal (BTUs/hr)
On Battery
(BTUs/hr)
3750
200
2275
< 1900
< 2400
3900
208
2375
< 2000
< 2400
4125
220
2525
< 2000
< 2500
4300
230
2675
< 2100
< 2600
4500
240
2775
< 2200
< 2700
UPS Physical Specifications
Parameter
PPU
Battery Module
Bypass Distribution Module
Height
283 mm (11.13
I
)
142.5 mm (5.61
I
)
283 mm (11.13
I
)
Width
252 mm (9.91
I
)
252 mm (9.91
I
)
252 mm (9.91
I
)
Depth
Plug/Receptacle: 406 mm (16
I
)
Hardwired: 463 mm (18.25
I
)
400 mm (15.75
I
)
Plug/Receptacle: 406 mm (16
I
)
Hardwired: 463 mm (18.25
I
)
Weight
18 kg (39 lb)
23.6 kg (52 lb)
37 kg (82 lb)