AUX DC Inverter Free Match 50HZ
R32
204
Notes
Drainage pipe and connection piping should be wrapped by heat insulation material
respectively lift the air conditioner is proved my dew conditioner experiment. But if it keeps on
working in high humidity (the dew temperature is more than23
℃
) environment which may lead to
water leakage, please use following additional insulation material:
◇
Glass fiber insulation material with the thickness between 10~20mm can be used.
◇
The part of indoor unit which get in touch with the back side of ceiling should pasted with
insulation material.
◇
Besides the previous more than 8mm thick insulation material, connection piping (both gas
pipe and liquid pipe), drainage pipe should be wrapped by additional 10~30 mm thick insulation
material.
Seal the hole on the wall.
◇
To prevent rainwater or other foreign bodies from entering the room and air-conditioner, the
gap between wall hole and tubing, drain pipe and electric wire should be sealed with mastic,
sealant rubber or putty.
◇
If the outdoor unit is higher than indoor unit, tubing should be bent to ensure that the lowest
point of the tubing is lower than the wall hole to prevent rainwater entering the room or
air-conditioner along the piping system.
Summary of Contents for F Series
Page 1: ...1 Technical Manual DC Inverter Free Match R32 ...
Page 2: ...2 2019 07 ...
Page 7: ...7 Part1 General Information 1 Nomenclature Indoor Unit Outdoor Unit ...
Page 9: ...9 24K Btu h AMWM H24 4R3 J ...
Page 27: ...AUX DC Inverter Free Match 50HZ R32 27 ...
Page 30: ...AUX DC Inverter Free Match 50HZ R32 30 Part3 Piping System 1 14K 18K ...
Page 33: ...AUX DC Inverter Free Match 50HZ R32 33 3 36K ...
Page 70: ...AUX DC Inverter Free Match 50HZ R32 70 ...
Page 71: ...AUX DC Inverter Free Match 50HZ R32 71 3 Ceiling Floor 09K 12K 18K 929 660 245 841 205 ...
Page 74: ...AUX DC Inverter Free Match 50HZ R32 74 5 Outdoor Unit 5 1 14K 18K 545 800 545 822 315 315 ...
Page 75: ...AUX DC Inverter Free Match 50HZ R32 75 5 2 21K 27K 834 540 655 854 335 328 ...
Page 76: ...AUX DC Inverter Free Match 50HZ R32 76 5 3 36K 42K 985 675 808 1000 409 395 ...
Page 80: ...AUX DC Inverter Free Match 50HZ R32 80 ...
Page 82: ...AUX DC Inverter Free Match 50HZ R32 82 3 Ceiling Floor 09k 12k 18k ...
Page 83: ...AUX DC Inverter Free Match 50HZ R32 83 4 Duct 07K 09K 12K 18K ...
Page 92: ...AUX DC Inverter Free Match 50HZ R32 92 Part8 Static pressure curve 1 07K 09K Duct ...
Page 93: ...AUX DC Inverter Free Match 50HZ R32 93 2 12K Duct ...
Page 94: ...AUX DC Inverter Free Match 50HZ R32 94 3 18K Duct ...
Page 103: ...AUX DC Inverter Free Match 50HZ R32 103 XK 04 Detailed operation instructions 6 ...
Page 158: ...AUX DC Inverter Free Match 50HZ R32 158 2 Cassette 09K 12K 18K ...
Page 164: ...AUX DC Inverter Free Match 50HZ R32 164 ...
Page 166: ...AUX DC Inverter Free Match 50HZ R32 166 4 2 18K ...
Page 168: ...AUX DC Inverter Free Match 50HZ R32 168 5 Outdoor Unit 5 1 14K 18K ...
Page 170: ...AUX DC Inverter Free Match 50HZ R32 170 5 2 21K 27K ...
Page 171: ...AUX DC Inverter Free Match 50HZ R32 171 ...
Page 173: ...AUX DC Inverter Free Match 50HZ R32 173 5 3 36K ...
Page 176: ...AUX DC Inverter Free Match 50HZ R32 176 5 4 42K ...
Page 183: ...AUX DC Inverter Free Match 50HZ R32 183 4 Cassette 4 1 Installation drawing ...
Page 184: ...AUX DC Inverter Free Match 50HZ R32 184 4 2 The distance between indoor unit and obstacle ...
Page 189: ...AUX DC Inverter Free Match 50HZ R32 189 ...
Page 196: ...AUX DC Inverter Free Match 50HZ R32 196 ...
Page 211: ...AUX DC Inverter Free Match 50HZ R32 211 1 2 21K 27K Main PCB and Driver modular ...
Page 212: ...AUX DC Inverter Free Match 50HZ R32 212 1 3 36K 42K Main PCB ...
Page 213: ...AUX DC Inverter Free Match 50HZ R32 213 Drive Modular Board ...
Page 214: ...AUX DC Inverter Free Match 50HZ R32 214 2 Indoor Unit PCB 2 1 09K 12K 18K Cassette ...
Page 215: ...AUX DC Inverter Free Match 50HZ R32 215 2 2 09K 12K 18K Ceilling Floor ...
Page 216: ...AUX DC Inverter Free Match 50HZ R32 216 2 3 07k 09K 12K 18K Duct ...
Page 220: ...AUX DC Inverter Free Match 50HZ R32 220 ...
Page 222: ...AUX DC Inverter Free Match 50HZ R32 222 Outdoor protection phase sequence ...
Page 224: ...AUX DC Inverter Free Match 50HZ R32 224 Heating high pressure protection ...
Page 225: ...AUX DC Inverter Free Match 50HZ R32 225 2 4 H6 low pressure protection ...
Page 226: ...AUX DC Inverter Free Match 50HZ R32 226 Cooling low pressure protection ...
Page 227: ...AUX DC Inverter Free Match 50HZ R32 227 Heating low pressure protection ...
Page 228: ...AUX DC Inverter Free Match 50HZ R32 228 ...
Page 230: ...AUX DC Inverter Free Match 50HZ R32 230 Heating exhaust temperature protection ...
Page 231: ...AUX DC Inverter Free Match 50HZ R32 231 ...
Page 232: ...AUX DC Inverter Free Match 50HZ R32 232 2 6 H8 four way valve failure protection ...
Page 233: ...AUX DC Inverter Free Match 50HZ R32 233 ...
Page 234: ...AUX DC Inverter Free Match 50HZ R32 234 2 7 Sensor failure protection ...