AUX air conditioner service manual
35
⑹
Ventilation mode
Under ventilation mode, the outdoor unit is always off, and the indoor fan runs according to the
default wind-speed. The remote control can be set with three types wind-speed, e.g. high fan, low fan
and silent fan except the strong fan; The operation condition of the air door is same as the one under
the refrigeration mode; The mode includes the function of timing, auto-restart (optional), negative ion
(optional), I feel
(
optional
)
.
Heating mode
⑺
The default temperature is determined by the remote control and to be within the range of 16
℃
- 32 ,
℃
which can be adjusted by the button of “+” and “-”. Press the button of “fan speed selection” for
choosing the wind speed from the four gears of strong fan, high fan, low fan and mute fan. The other
conditions are as following, when:
①
TA-3-TS
≤
-1
℃,
if after three minutes delay time as for protection purpose, the compressor and the
outdoor fan start, the indoor fan works in cold-wind prevention condition, the TA shown on the digital
display has 3
℃
temperature compensation.
②
TA-3-TS
≥
1
℃,
if the compressor last continuously running for 3minutes, the compressor and the
outdoor fan stop, the indoor fan keeps on working under anti cold-wind condition. The TA shown on
the digital display has 3
℃
temperature compensation.
③
TA-3=TS
,
retain the previous status
;
④
Automatic wind speed control, when:
TA
<
TS
,
wind speed in high fan
;
TS
≤
TA
<
TS +2
℃,
wind speed in middle fan
;
TA
≥
TS + 2
℃,
wind speed in low fan
;
When wind speed turns from the low fan to high fan without 3 minutes protection delay; wind speed
turns from the high fan to low fan with 3 minutes protection delay
;
⑤
When the heating process is ongoing, the button of the “Swing” can control and stop the swing
leaves; When swing works freely, the maximum angle of the swing leaves is 50°e.g. the swinging
status between 3-5 (refer to picture 3);
⑥
There is no 3 minutes’ delay protection for electrifying the compressor initially. The compressor
starts 10 seconds later after the start of the four-way valve. The outdoor fan starts 2 seconds later after
the start of the compressor; Low down TS to be
<
TA-3
,
then the compressor turns off immediately
without the restriction condition of 3 minutes protection delay;
The mode includes the functions of timing, sleeping, auto
⑦
-restart (optional), negative ion (optional),
I feel
(
optional
)
⑧
The four-way valve starts immediately once being electrified.10 seconds later the compressor starts;
Under the compressor opening condition, the four-way valve shuts off after 2 minutes and 50 seconds
delay protection when turn off or switch the controller; The four-way valve turns off immediately after
turning off the controller when the compressor is off;
Summary of Contents for E Series
Page 1: ......
Page 32: ...AUX air conditioner service manual The other parts 29 ...
Page 33: ...AUX air conditioner service manual 30 ...
Page 102: ...AUX air conditioner service manual 99 Outdoor unit exploded picture ...
Page 104: ...AUX air conditioner service manual 101 2 ASW H09A4 EC Indoor unit exploded picture ...
Page 106: ...AUX air conditioner service manual 103 Outdoor unit exploded picture ...
Page 108: ...AUX air conditioner service manual 105 3 ASW H12A4 ET Indoor unit exploded picture ...
Page 110: ...AUX air conditioner service manual 107 Outdoor unit exploded picture ...
Page 112: ...AUX air conditioner service manual 109 4 ASW H12A4 EC Indoor unit exploded picture ...
Page 114: ...AUX air conditioner service manual 111 Outdoor unit exploded picture ...
Page 116: ...AUX air conditioner service manual 113 5 ASW H18B4 ET Indoor unit exploded picture ...
Page 118: ...AUX air conditioner service manual 115 Outdoor unit exploded picture ...
Page 120: ...AUX air conditioner service manual 117 6 ASW H24B4 ET Indoor unit exploded picture ...
Page 122: ...AUX air conditioner service manual 119 Outdoor unit exploded picture ...
Page 126: ...AUX air conditioner service manual 123 Outdoor unit exploded picture ...
Page 128: ...AUX air conditioner service manual 125 2 ASW H09A4 HSL Indoor unit exploded picture ...
Page 130: ...AUX air conditioner service manual 127 Outdoor unit exploded picture ...
Page 132: ...AUX air conditioner service manual 129 3 ASW H09A4 HS Indoor unit exploded picture ...
Page 134: ...AUX air conditioner service manual 131 Outdoor unit exploded picture ...
Page 136: ...AUX air conditioner service manual 133 4 ASW H18B4 HS Indoor unit exploded picture ...
Page 138: ...AUX air conditioner service manual 135 Outdoor unit exploded picture ...
Page 140: ...AUX air conditioner service manual 137 5 ASW H24B4 HS Indoor unit exploded picture ...
Page 142: ...AUX air conditioner service manual 139 Outdoor unit exploded picture ...
Page 146: ...AUX air conditioner service manual 143 Outdoor unit exploded picture ...
Page 148: ...AUX air conditioner service manual 145 2 ASF H41A5 C Indoor unit exploded picture ...
Page 149: ...AUX air conditioner service manual 146 ...
Page 151: ...AUX air conditioner service manual 148 Outdoor unit exploded picture ...
Page 166: ...AUX air conditioner service manual 163 ...
Page 240: ......