4 Cooling mode
8.Function Exposition
1.When TA-TS>1 C and it is operated after the compressor protection duration ,the
compressor and outdoor fan motor will be running;
2.When TA equals TS, the status will be the same as item 1;
3.When TA-TS<-1 C and it is operated after the compressor protection duration, the
compressor and outdoor fan motor will be running;
4.At this mode, the fan speed can be set with remote control while the indoor fan motor
will keep running;
5.When the state of TE<0 C lasts for 10s and the compressor keeps running for over 5
minutes, the indoor fan motor will run at set speed ,if the compressor and outdoor fan
motor are power off; when TE>7 C, it will quit this protection function;
6.At this mode, timer, sleep, memory, negative ion, I feel functions are available;
7.Once cooling mode is set, the movement of louver can be controlled by remote control;
8.Automatic fan speed control:
When TA-TS>3 C,the fan motor works at high speed;
When TS+1 C<TA<TS+3 C,the fan motor works at medium speed;
When TA-TS<1 C,the fan motor works at low speed;
If the fan speed is to be shifted from low to high, the 3-minute protection will be off, and it
will be on when fan speed is to be shifted from high to low.
9.When first powered, the 3-minute compressor protection will be off and the outdoor fan
motor will be running after the compressor is on for 2s;if TS is set higher than TA, the
compressor will be off immediately without the protection function;
10.When TE >64 C for 10s , the compressor and outdoor fan motor are off and the
compressor can be well started after TE<62 C, then the indoor fan motor will run at set speed
if it is set manually when over-heat protection is on. The indoor fan will run at low speed if it
is set automatic fan speed.
The temperature is controlled by pressing the + or -button on the remote control between 16 C
and 32 C.You can select fan speed from Low, Med, High, Auto. The 4-way valve will keep
closed at this mode, and other status are demonstrated as follows:
8-5 Dehumidifying Mode
1.The 4-way valve will keep closed at this mode with the controllable temperature between
16 C t o 32 C ;
2.After the duration of 3-minute protection, the compressor and outdoor fan motor will work
as follows:
(1).When TA>TS+2 C, the compressor and outdoor fan motor will run continuously at set speed;
(2).When TS<TA<TS+2 C and the compressor and outdoor fan motor are on for 10 minutes
and off for 6 minutes, then the indoor fan will be off when the compressor is off in the
duration of 3-minute protection. The indoor fan will run at slight speed at under other
conditions;
(3).When TA<TS, the compressor and outdoor fan motor stops running, and the indoor fan
motor will run at slight speed after being off for 3 minutes.
Automatic fan speed control:
When TA-TS>5 C, the fan motor runs at high speed;
When TS+3 C<TA<TS+5 C,the fan motor runs at medium speed;
When TS+2 C<TA<TS+3 C,the fan motor runs at low speed;
When TS<TA<TS+2 C, the fan motor runs at slight speed;
When TA<TS, the indoor fan motor will stop in the duration of 3-minute protection and run
at slight speed after the duration.
Summary of Contents for ASW-09A4/E Series
Page 3: ...2 1 Appearance 2 Technical Specification 2 ...
Page 4: ...OUTDOOR UNIT INDOOR UNIT 2 1 Appearance continue 2 Technical Specification 3 ...
Page 15: ...4 Wiring Diagram 4 1 ASW H 24B4 E Indoor Unit 14 ...
Page 27: ...Fig 2 1 26 6 Explosion View And Parts List 6 3 door Unit Explosion View Of Out ...
Page 44: ......