DC inverter ARV Individual Series technical manual
87
3.8Electric Characteristic
Model
Unit
Power supply
OFM
Hz
Voltage
(V)
MCA
(A)
MFA
(A)
Output power
(W)
FLA
(A)
ARV-H615/5R1B
50
380-415V
36.20
50
750*2
3.50
ARV-H670/5R1B
50
380-415V
41.90
50
750*2
3.50
ARV-H730/5R1B
50
380-415V
57.90
80
750*3
3.50
ARV-H78
0
/5R1B
50
380-415V
58.86
80
750*3
3.50
ARV-H850/5R1B
50
380-415V
64.13
80
750*3
3.50
ARV-H900/5R1B
50
380-415V
65.28
80
750*3
3.50
Symbols:
MCA:
Min. Circuit Amps. (A);
MFA:
Max. Fuse Amps. (A);
OFM:
Outdoor Fan Motor;
FLA:
Full Load Amps. (A);
Note:
1. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB.
2. Maximum allowable voltage variation between phase and phase is 2%.
3. Selection wire size based on the larger value of MCA.
4. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).
Summary of Contents for ANB66FVAMT
Page 1: ...AUX DC inverter ARV individual series 1 Technical Manual DC Inverter ARV Individual Series ...
Page 3: ...AUX DC inverter ARV individual series 3 ...
Page 19: ...AUX DC inverter ARV outdoor unit individual series technical manual 16 ...
Page 21: ...AUX DC inverter ARV outdoor unit individual series technical manual 18 ...
Page 96: ...AUX DC inverter ARV outdoor unit individual series technical manual 93 ...
Page 113: ...AUX DC inverter ARV outdoor unit individual series technical manual 110 ...
Page 127: ...AUX DC inverter ARV outdoor unit individual series technical manual 124 ...