118
2. Commissioning procedure
2.1 Cooling Commissioning procedure
System confirmation
Indoor units confirmation
Outdoor units confirmation
Whether the subordinate unit can
work normally
Whether indoor unit blows air at normal
air speed, whether there is abnormal
noise in indoor and outdoor units
After the stable operation of the system (normal
operation last for 1 hour), write down the
operation parameters,
Whether there is something wrong with indoor
units, solve failures according to failure code
.
Analysis the data according to parameters in table 1
After eliminating the problem, turn off the indoor unit one by
one to confirm whether the electric expansion valve of the
stand by indoor unit can be closed or not).
After stable operation (at last for 1 hour), write down operation
parameters as in table 1, and analysis the data.
Eliminate fault, system operation confirmed, refrigeration commissioning completed.
Make sure the outdoor unit canfind all the indoor units.
Start up all the indoor units in cooling mode with high fan speed
and setting temperature of 16
℃
Summary of Contents for ANB66FVAMT
Page 1: ...AUX DC inverter ARV individual series 1 Technical Manual DC Inverter ARV Individual Series ...
Page 3: ...AUX DC inverter ARV individual series 3 ...
Page 19: ...AUX DC inverter ARV outdoor unit individual series technical manual 16 ...
Page 21: ...AUX DC inverter ARV outdoor unit individual series technical manual 18 ...
Page 96: ...AUX DC inverter ARV outdoor unit individual series technical manual 93 ...
Page 113: ...AUX DC inverter ARV outdoor unit individual series technical manual 110 ...
Page 127: ...AUX DC inverter ARV outdoor unit individual series technical manual 124 ...