1
SENSOR RESISTANCE
Sensor resistance is measured at the two middle wires of the 4-wire cable contact.
Supply water sensor T1 Outdoor sensor T2
OPTIONALS
AUTOMIX 10RB is a room sensor for measuring and
setting the temperature inside the house.
AUTOMIX 10RB should be installed if the room tem-
perature fluctuates because the building is affected
by sunlight or wind.
A green LED indicates that power is on. When the
motor runs, the LED dims slightly.
AUTOMIX10RC is a remote control designed for
floor heating systems. It is used to conveniently
adjust/parallel displace the heating graph. Sup-
ply water temperaure can be lowered 9 °C or
raised 6 °C. AUTOMIX 10RC corresponds to the
function parallel displacement F.
A green LED indicates that power is on. When the
motor runs, the LED dims slightly.
TECHNICAL DATA
Type of control
PI-control with microprocessor
Voltage
18 VAC 50/60 Hz
Adapter
230/18 VAC 200 mA with 1,7 m wire
Power consumption
3 VA
Torque
5 Nm
Angle of rotation
90°
Heating graphs
1 to 9, stepless
Parallel displacement
+/- 10°C supply water temperature, stepless
Min. supply water limiter
+15°C to +35°C supply water temperature
Max.supply water limiter
+40°C to 90°C supply water temperature
Room sensor AM 10RB
+12°C to 27°C room temperature, stepless
Remote control AM 10RC
-9°C to +6°C supply water temperature, stepless
Manual operation
Yes, in case of power failure
Ptotection class
IP 40
Dimensions
80 x 90 x 93 mm
Weight
0,53 kg