1
WIRING
Automix 10 is delivered with wires. The main supply
and all sensors have plug-in connections.
The quick do-it-your-self installation minimizes
installation problems.
Left side of motor
A. Adapter
B. Supply water
sensor T1
Right side of
motor
C. Outdoor
sensor T2
D. Heating
graphs
Motor under the cover
Connection E is placed under the motor cover.
Room sensor Automix 10RB and remote control
Automix 10RC are connected to E.
The cover has edge cuttings for the wire.
GRAPH SETTING
The regulating graph for a certain house is
dependent on dimensions, location, insulation etc.
Therefore it is not possible to decide on a graph in
advance. It has to be tried out. The graph is set with
knobs D and F. The knobs work steplessly.
Initial setting
Regulating graph for radiator heating, set knob D
on 6. Regulating graph for floor heating, set knob
D on 3.
Room temperature setting/parallel displacement
For parallel displacement / to obtain the desired
room temperature use knob F. The supply water
temperature can be raised or lowered steplessly by
10 °C from setting 0. A supply water temperature
of 2,5 ºC corresponds to 1 ºC in room temperature.
Adjustments
Should the room temperature rise with falling
outdoor temperature: lower knob D raise knob F
Should the room temperature fall with falling
outdoor temperature: raise knob D lower knob F
Make only minor changes with knobs D and F.
When the house has an even room temperature
despite fluctuating outdoor temperatures, the
correct regulating graph has been obtained.
N.B! Heat affects slowly. When a temperature setting
has been changed it takes several hours before the
room temperature corresponds to the new setting
due to dimensions of the heating system and the
insulation of the house. A floor heating system
responds even slower to a new setting than a
radiator system.
english