background image

1

Sales 800-633-0405

www.productivity1000.com

TC1+

TC2+

TC2-

TC3+

TC3-

TC4+

TC4-

TC1-

P1-04THM

THERMOCOUPLE

INPUT

1000

P1-04THM Analog Input

The P1-04THM Thermocouple Input Module 

provides  four  differential  channels  for  receiving 

thermocouple and voltage input signals for use with 

the Productivity1000 system.

Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . .  1

General Specifications  . . . . . . . . . . . . . . . . . . . . . .  2

Removable Terminal Block Specifications. . . . . . . .  2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . .  3

Module Installation Procedure . . . . . . . . . . . . . . . . .  4

QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Module Configuration  . . . . . . . . . . . . . . . . . . . . . . .  5

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement (See www.productivity1000.com for details).

Terminal Block Included. Not Compatible with ZIPLink.

Thermocouple Input Specifications

Input Channels

4 differential

Data Format

Floating Point

Common Mode Range

±1.25 V

Common Mode Rejection

100dB @ DC

Input Impedance

>5M

Maximum Ratings

Fault Protected Inputs to ±50V

Resolution

16-bit, ±0.1 °C or °F

Thermocouple Input Ranges

Type J  -190° to 760°C (-310° to 1400°F)
Type E - 210° to 1000°C (-346° to 1832°F)
Type K  -150° to 1372°C (-238° to 2505°F)
Type R    65° to 1768°C (149° to 3214°F)
Type S    65° to 1768°C (149° to 3214°F)
Type T  -230° to 400°C (-382° to 752°F)
Type B   529° to 1820°C (984° to 3308°F)
Type N  -70° to 1300°C (-94° to 2372°F)
Type C   65° to 2320°C (149° to 4208°F)

Thermocouple Linearization

Automatic

Cold Junction Compensation

Automatic

Sample Duration Time

270ms

All Channel Update Rate

1.08 s

Open Circuit Detection Time

Within 5s

Conversion Method

Sigma-Delta

Accuracy vs. Temperature

±50ppm per °C (maximum)

Maximum Inaccuracy

±3°C maximum (excluding thermocouple error)

Linearity Error

±1°C maximum (±0.5 °C typical)
Monotonic with no missing codes

Warm-up Time

30 minutes for ±1% repeatability
2 minutes to reach voltage specifications

External Power Supply 

Required

None