1
Sales 800-633-0405
www.productivity1000.com
TC1+
TC2+
TC2-
TC3+
TC3-
TC4+
TC4-
TC1-
P1-04THM
THERMOCOUPLE
INPUT
1000
P1-04THM Analog Input
The P1-04THM Thermocouple Input Module
provides four differential channels for receiving
thermocouple and voltage input signals for use with
the Productivity1000 system.
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 1
General Specifications . . . . . . . . . . . . . . . . . . . . . . 2
Removable Terminal Block Specifications. . . . . . . . 2
Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3
Module Installation Procedure . . . . . . . . . . . . . . . . . 4
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Warranty: Thirty-day money-back guarantee. Two-year limited
replacement (See www.productivity1000.com for details).
Terminal Block Included. Not Compatible with ZIPLink.
Thermocouple Input Specifications
Input Channels
4 differential
Data Format
Floating Point
Common Mode Range
±1.25 V
Common Mode Rejection
100dB @ DC
Input Impedance
>5M
Ω
Maximum Ratings
Fault Protected Inputs to ±50V
Resolution
16-bit, ±0.1 °C or °F
Thermocouple Input Ranges
Type J -190° to 760°C (-310° to 1400°F)
Type E - 210° to 1000°C (-346° to 1832°F)
Type K -150° to 1372°C (-238° to 2505°F)
Type R 65° to 1768°C (149° to 3214°F)
Type S 65° to 1768°C (149° to 3214°F)
Type T -230° to 400°C (-382° to 752°F)
Type B 529° to 1820°C (984° to 3308°F)
Type N -70° to 1300°C (-94° to 2372°F)
Type C 65° to 2320°C (149° to 4208°F)
Thermocouple Linearization
Automatic
Cold Junction Compensation
Automatic
Sample Duration Time
270ms
All Channel Update Rate
1.08 s
Open Circuit Detection Time
Within 5s
Conversion Method
Sigma-Delta
Accuracy vs. Temperature
±50ppm per °C (maximum)
Maximum Inaccuracy
±3°C maximum (excluding thermocouple error)
Linearity Error
±1°C maximum (±0.5 °C typical)
Monotonic with no missing codes
Warm-up Time
30 minutes for ±1% repeatability
2 minutes to reach voltage specifications
External Power Supply
Required
None