Automationdirect.com Productivity 1000 P1-04THM Manual Download Page 3

3

Sales 800-633-0405

www.productivity1000.com

P1-04THM Schematic

TC1+
TC1-
TC2+
TC2-

TC3+

TC4+

TC3-

TC4-

CH1 T/C

INPUT

INTERNAL

MODULE CIRCUITRY

CH2 T/C

INPUT

CH3 T/C

INPUT

CH4 T/C

INPUT

123456789

10

P1-04THM  Wiring Diagram

AC or DC

AC or DC

Thermocouple Input Circuits

Voltage Input Circuits

Excitation

Power Supply

Transmitter

Power Supply

Ungrounded/Shielded

Thermocouple

TC+

TC-

TC+

TC-

TC+

TC-

Grounded/Shielded

Thermocouple

Infrared

Thermocouple

4-wire

Voltage

Transmitter

Load Cell

or

Strain Gauge

Voltage Divider

TC+

TC-

TC+

TC-

TC+

TC-

NOTES: 

1.  Connect shield to thermocouple signal/ground only. Do not connect to 

both ends.

2.  Install jumper wire on each unused input, 

    TC+ to TC-.

3.  With grounded thermocouples, take precautions to prevent having a 

voltage potential between thermocouple tips. A voltage of 1.25V or 

greater between tips will skew measurements.

4.  Use shielded, twisted thermocouple extension wire that matches the 

thermocouple type. Use thermocouple-compatible junction blocks.

TC+

TC-

Reviews: