Before installing the module, verify power to the PLC is turned off. To install the ECOM
module, line up the module’s printed circuit board with the grooves in the base and push
the module until it is flush with face of the DL205 base power supply. If you feel more than
moderate resistance when you push the module into the base, the circuit board may not be
aligned with the grooves in the base. When the module is firmly seated in the slot, depress the
top and bottom retaining clips to lock the module in place.
NOTE:
When adding modules to your PLC always confirm that your power budget will accommodate the
added module. See the User Manual for your PLC for more information about calculating the power budget.
See Appendix A for the power consumption of the ECOM modules.
Module Type
CPU
CPU - Base
Usuable Slots
H2-ECOM
D2-240
D2-03B-1, D2-03BDC1-1, D2-03BDC-2
1
H2-ECOM100
D2-250-1
D2-04B-1, D2-04BDC1-1, D2-04BDC-2
1, 2
H2-ECOM-F
D2-260
D2-06B-1, D2-06BDC1-1, D2-06BDC-1
1, 2, 3, 4
D2-262
D2-09B-1, D2-09BDC1-1, D2-09BDC-1
1, 2, 3, 4, 5, 6, 7