Introduction
7
7
Data Communications Module, 2nd Edition, 2/03
Specifications
Operating Temperature
32
°
F to 131
°
F (0
°
to 55
°
C)
Storage Temperature
–4
°
F to 158
°
F (–20
°
to 80
°
C)
Operating Humidity
5 to 95% (non-condensing)
Air Composition
No corrosive gases permitted
Vibration
JIS C0040
Shock
JIS C0041
Voltage Isolation
1500 VAC, 1 minute duration
Insulation Resistance
10M ohms at 500 VDC
Noise
NEMA ICS3–304
Power Budget Requirement
300ma @ 5 VDC
Maximum number of modules
limited only by power budget
CPU Required
D2–240/250–1/260 minimum
firmware V1.8 or later
Location of module
CPU base only
any slot except Slot 0 or CPU slot
Interface
Serial RS232C / RS422
half-duplex, DTE, Asynchronous,
8 bits/character, odd or no parity
Baud Rates
300 to 38.4K baud, switch selectable
Maximum Distance
RS232C – 49ft (15 meters)
RS422 – 3300 feet (1000 meters)
Protocol
Direct
NET
1
K-sequence (proprietary)
MODBUS
RTU
Diagnostics
Automatic check of ROM/RAM,
communications, switch settings,
and LEDs
Note 1:
Also compatible with Hostlink and/or CCM2 protocols. These names were used by previous vendors of
compatible Koyo designed products.
Environmental
Specifications
Operating
Specifications
Summary of Contents for D2-DCM
Page 4: ...D2 DCM Data Communications Module Manual Number D2 DCM M...
Page 37: ...1A Cable Diagrams...
Page 47: ...Data Communications Module 2nd Edition 2 03 B RLL Communications Programs...
Page 58: ...Data Communications Module 2nd Edition 2 03 C Using the D2 DCM with MODBUS...
Page 67: ...Data Communications Module 2nd Edition 2 03 D Using the D2 DCM with Modems...