MODBUS R
T
U
D0–DCM with
5–4
D0–DCM Using MODBUS
DL05/06 Data Communications Module, 1st Edition, 08/05
DL06 Memory Type
QTY
(Dec.)
PLC Range
(Octal)
MODBUS
Address Range
MODBUS
Data Type
For Discrete Data Types .... Convert PLC Addr. to Dec. + Start of Range + Data Type
Inputs (X)
512
X0
–
X777
2048
–
2560
Input
Special Relays (SP)
512
SP0
–
SP777
3072
–
3583
Input
Outputs (Y)
512
Y0
–
Y777
2048
–
2560
Coil
Control Relays (C)
1024
C0
–
C1777
3072
–
4095
Coil
Timer Contacts (T)
256
T0
–
T377
6144
–
6399
Coil
Counter Contacts (CT)
128
CT0
–
CT177
6400
–
6527
Coil
Stage Status Bits (S)
1024
S0
–
S1777
5120
–
6143
Coil
Global Inputs (GX)
2048
GX0
–
GX3777
0
–
2047
Input
Global Outputs (GY)
2048
GY0
–
GY3777
0
–
2047
Coil
For Word Data Types .... Convert PLC Addr. to Dec. + Data Type
Timer Current Values (V)
256
V0 – V377
0
–
255
Input Register
Counter Current Values (V)
128
V1000
–
V1177
512
–
639
Input Register
V Memory, user data (V)
256
3072
4096
V400 – V677
V1400 – V7377
V10000 – V17777
256
–
511
768
–
3839
4096
–
8191
Holding Register
Summary of Contents for D0-DCM
Page 1: ...D0 DCM Data Communications Module Manual Number D0 DCM M...
Page 8: ......
Page 9: ...1 1 Introduction In This Chapter Manual Overview D0 DCM Hardware Features D0 DCM Applications...
Page 24: ......
Page 56: ......
Page 57: ...1 5 D0 DCM Using MODBUSr RTU In This Chapter Network Slave Operation Network Master Operation...