DCM Port
Configuration
Installation and
Safety Guidelines
3–10
D0–DCM Setup
DL05/06 Data Communications Module, 1st Edition, 08/05
Word +0007 is used for Port 1 and Port 2 to :
•
request that the DCM recognizes changes in the port(s) communication
parameters from default or previous settings
•
confirm that Port 1 and Port 2 configuration is complete
MSB
LSB
0
7 6 5 4 3 2 1
Port Configuration
Completion Code
word +0007
1
5
Set all unused
bits to zero.
Loading a K0055 (BCD) into word +0007 will request that the DCM recognizes (looks for) new
or desired port communication parameters that are written to the DCM port configuration
registers. If the requested changes are valid, a 00AA (hex) will then be written to word +0007.
If the desired or new communications are invalid or out of range, an error code 00E* (Hex) will
be written to word +0007. The last digits indicate the address that has an error. For example,
error code 00E2 means that word +0002 has an error.
Use word +0024 to set Port 1 and Port 2:
•
Reset Time–out in seconds
The communication port will reset after the specified time after the port goes from the BUSY
state to the IDLE state.
MSB
LSB
0
1
1
1
0 9 8 7 6 5 4 3 2 1
Port 2 Reset
Time–out
(BCD)
1
5
1
4
1
3
1
2
word +0024
Port 1 Reset
Time–out
(BCD)
Reset Time–out
Port
Time(s)
Function
Port 1: Bit 0–7
0
Disable
Port 1: Bit 0 7
Port 2: Bit 15–8
1–99
Enable
F: Port 1 and 2
Setup and
Completion Code
G: Port 1 and 2
Reset Time–out