Installation and Setup
Installation and
Safety Guidelines
2–8
Installation and Setup
DL05/06 Data Communications Module, 1st Edition, 08/05
Module Specifications
Power Budget Requirement
250mA @ 5 VDC
(not including external 5VDC consumption)
Maximum Number of Modules
DL05: 1; DL06: 4
Operating Temperature
32
°
F to 131
°
F (0
°
to 55
°
C)
Storage Temperature
–4
°
F to 158
°
F (–20
°
to 80
°
C)
Operating Humidity
5 to 95% (non-condensing)
Air Composition
No corrosive gases permitted
Vibration
MIL STD 810C, Method 514.2
Shock
MIL STD 810C, Method 516.2
Voltage Isolation
1000 VAC, 1 minute duration
Insulation Resistance
10M ohms at 500 VDC
Noise
Immunity
NEMA ICS3–304, UL, CE, (FCC Class A)
Class 1, Division 2 (C1D2)
Weight
1.75 oz. (50g)
Connector
6–pin female modular (RJ12)
Communications
RS–232
Protocol
(auto–dectection)
DirectNET slave
K-sequence slave
MODBUS
®
RTU slave
Station Number
0 – 247
Communication Data
8 data bits, 1 start bit, 1 stop bit (fixed)
Parity Bit
None, Odd
Baud Rates
9600, 19200, 38400, 57600, 115200 bps
Transmit Mode
ASCII, Hex
Maximum Distance
RS–232: 50ft (15 meters)
Port 1
Port 1 Pin Descriptions
1
0V
2
5V
3
RXD
Receive Data (RS–232)
4
TXD
Transmit Data (RS–232)
5
RTS
Request to Send
6
0V
1
2
3
4
5
6
General
Specifications
Port 1
Specifications
Summary of Contents for D0-DCM
Page 1: ...D0 DCM Data Communications Module Manual Number D0 DCM M...
Page 8: ......
Page 9: ...1 1 Introduction In This Chapter Manual Overview D0 DCM Hardware Features D0 DCM Applications...
Page 24: ......
Page 56: ......
Page 57: ...1 5 D0 DCM Using MODBUSr RTU In This Chapter Network Slave Operation Network Master Operation...