DCM Port
Configuration
Installation and
Safety Guidelines
3–8
D0–DCM Setup
DL05/06 Data Communications Module, 1st Edition, 08/05
Use word +0003 to set Port 2:
•
Station address ranges from 0–247 (00–F7 Hex)
•
Baud rates ranging from 9.6K to 115.2K bps
•
Data Bit Length (7 or 8 bits)
•
Stop Bit Length (1 or 2 bits)
•
Odd, Even or No Parity
MSB
LSB
0
1
1
1
0 9 8 7 6 5 4 3 2 1
Baud
Rate
Station
Address
1
5
1
4
1
3
1
2
Parity
word +0003
Data
Bit
Stop
Bit
Set all unused bits to zero.
Port 2: Station Address
Address
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
00
0
0
0
0
0
0
0
0
01
0
0
0
0
0
0
0
1
02
0
0
0
0
0
0
1
0
–––––
F6
1
1
1
1
0
1
1
0
F7
1
1
1
1
0
1
1
1
Port 2: Baud Rate
Baud Rate
Bit 11
Bit 10
Bit 9
Bit 8
300 bps
0
0
0
0
600 bps
0
0
0
1
1200 bps
0
0
1
0
2400 bps
0
0
1
1
4800 bps
0
1
0
0
9600 bps
0
1
0
1
19.K bps
0
1
1
0
38.4K bps
0
1
1
1
57.6K bps
1
0
0
0
115.2K bps
1
0
0
1
D: Port 2 –
Station Address,
Baud Rate,
Data Bit,
Stop Bit,
Parity
Summary of Contents for D0-DCM
Page 1: ...D0 DCM Data Communications Module Manual Number D0 DCM M...
Page 8: ......
Page 9: ...1 1 Introduction In This Chapter Manual Overview D0 DCM Hardware Features D0 DCM Applications...
Page 24: ......
Page 56: ......
Page 57: ...1 5 D0 DCM Using MODBUSr RTU In This Chapter Network Slave Operation Network Master Operation...