22
GDO-7V1 SecuraLift®
Owner Installation Instructions
21. Fitting the safety photo electric beam
sensor (optional)
Locate the Photo Electric Beam (P.E.) normally closed
contact type in a strategic location within doorway. We
recommend 150mm above the floor level and as close
as possible to the door opening, inside the garage.
Remove shunt from P.E connector
(Fig. 29)
and connect
the wires from the P.E. wiring harness to terminal block
(Fig. 30).
The wiring diagram is for Model PHBE (Order
Code 90214).
Make sure to align the beams correctly. Follow the
manual supplied with the Photo Electric Beam.
WARNING: When using Auto Close Mode and
P.E. beams, the doorway must be clear of all
obstructions and persons at all times. The
location of the beam and manner in which it is
installed might not give safety protection at all times.
Check to make sure that the height of the beam and
type used give maximum protection possible.
22. Setting of auto close time important notice:
it is compulsory to install a photo electric beam
before using the auto close mode.
The Auto Close timer will only start after the Photo
Electric Beams (P.E.) path is broken and the auto close
time has been set. If the P.E. path is not broken the
door will remain open till the path is broken. If the Door
Opener incurs an obstruction (not from the P.E.) while
closing the door will re-open and not auto close until
the part of the P.E. beam is broken again.
Setting auto close time
1. Press and hold the Auto Close Time button
(Fig. 31).
2. While holding in the Auto Close Time button, press
the Plus (+) button. Each press of this button wil add
one second to the auto close delay time.
3. To decrease the delay time follow Step 1 and press
the Minus (-) button. Each press will deduct one
second from the auto close time.
4. Press the Operate button or transmitter to open the
door. When the door is fully opened the Open Limit
green LED will flash to indicate that the auto close
mode is in operation. Break the path of the P.E. Beam
momentarily, this will initialize the auto close mode.
When the door reaches the fully opened position, the
door will pause for the set auto close time and start to
auto close.
P.E. Beam and auto close
Remove P.E. Shunt
29
fig
29
fig
29
fig
Model: PHBE
Receiver
Transmitter
Cable 1
Cable 2
Red (24V)
Yellow N/C)
Black (CDM)