Rudolf R2 User's Manual
3BConfiguration Sections - 16BBattery
•
37
4.7
Battery
Alt+B
The control unit will give an alarm if the start-battery voltage is too
low.
It will not alarm during Start (Cranking state), or during Stop
(Stopping state).
4.7.1
Start Battery Voltage
Select 12V or 24V supply. The control unit is a 24V system,
but if a 12/24DC/DC converter is used, select 12V here.
Otherwise, always choose 24V.
4.7.2
Low Battery Voltage Alarm
This field specifies the voltage where the control unit will issue
an alarm for low start-battery voltage.
Typical:
25.5 volt
24V Range: 18.0 – 30.0 volt
12V Range: 9.0 – 15.0 volt
4.7.3
Delay before Alarm
When the battery voltage is below limit, it must remain low for
this period, before the alarm is given.
Typical:
60 seconds
Range:
1 – 255 seconds