Rudolf R2 User's Manual
3BConfiguration Sections - 11BSwitch
•
25
Shutdown uses Normally Open contacts (NO).
It is possible to change that in this menu, although Rudolf suggests
the most commonly used switch type for Warning, Alarm and
Shutdown as above.
Switches for shutdowns shall be of type NO, as a broken wire
should not initiate a shutdown.
4.2.7
Warning/Alarm/Shutdown on RUN only
If selected, the Warning/Alarm/Shutdown activates only if the
engine is running.
4.2.8
Initial delay
An initial delay is possible only if “Warning/Alarm/Shutdown
on RUN only” is selected.
This is typically used on oil pressure sensors/switches.
The amount of time after the engine has started (RUN is
detected) until the channel is activated.
Typical value: 10-15 seconds
4.2.9
Broken Wire Detection
This feature can be applied on channels 1-6, if it is a shutdown
channel.
A
10k
ohm resistor must be connected in
parallel
with the
actual switch.
Refer to the control unit manual for further details.
4.2.10
Delay before alarm/shutdown
When the sensor is outside limit the control panel issues a
warning, alarm or shutdown (depending on what is configured)
after this amount of time.
Typical value: 2 seconds