28
•
3BConfiguration Sections - 12BAnalog In
Rudolf R2 User's Manual
The alarm “Cooling Water Temp.” appears two seconds
after the temperature exceeds 92 degrees C.
4.3.2
Active
This enables the input channel for use. Any channel can be
enabled (
) or disabled (
).
If the channel is disabled, the bargraph will not be displayed.
4.3.3
Input Type
This may be 0-20mA or 4-20mA.
On channel 1 only, 0-10V can be selected.
4.3.4
Description
The text that describes the sensor, or its function. The text can
be up to 30 characters long and may consist of numbers and, to
some extent, national characters.
Note
: Although you can type up to 30 characters, we
recommend a maximum of 20 characters, as this gives a nicer
view.
Rudolf will not allow typing of characters the control unit is
unable to display.
4.3.5
Sensor Range
The sensor range, as given on the sensor, must be completed for
the meter to display correctly. The range can be set with one
decimal.
The 4mA signal will equal the minimum (here 0 Bar) and 20mA
will indicate the maximum (here 10 Bars) on the control unit
meter.
The range is –3000..3000.
4.3.6
Units
Select a predefined unit or type a new. Maximum four characters.
This will be displayed at the end of the meter in the control unit.
4.3.7
Limit
Optionally, type a limit for the meter, inside the set sensor
range. This will be displayed on the meter as a vertical bar.