background image

 
 
 
 
 
 
 

 

 

page -

  

18

  

-

  

Australian Hydronic Supplies 

10 Frankston Gardens Drive 

Carrum Downs, Victoria,  

Australia  3201 

8.4 Pipe in screed installation method  

1.

 

Install  Polystyrene  insulation  over  the  concrete 
slab 

2.

 

Place  polyethylene  membrane  over  the 
insulation.  Membrane  prevents  escape  of  the 
water from the screed.  

3.

 

Install  sound  insulating  edge  strip  along  walls 
and  around  ascending  structural  components.  
E.g. door frames or columns. 

4.

 

Edge  insulating  strip  is  made  from  closed  cell 
PE  foam  and  it  allows  for  the  expansion  of  the 

heated  screed  and  prevents  thermal  and 
acoustic bridging to the outside wall. 

5.

 

Install  pipes  in  either  classic  serpentine  or 
compacted  marginal  zone  serpentine  lying 
pattern. 

6.

 

Integrated  marginal  zone  serpentine  laying 
pattern  provides  more  even  temperature 
distribution 

across 

the 

floor

8.4.1 Filling the system 

1.

 

The circuits must be flushed with water so that 
they  are  free  from  air.  The  individual  heating 
circuits  are  flushed  consecutively,  during 
which the heating valves for each other circuit 
must be closed.  

2.

 

Proceed as follows:- 

3.

 

Check that all manifold connections are tight. 

4.

 

Close  fully  ALL  Flow  valves  and  ALL  return 
valves. 

5.

 

Connect a hose to the flow Drain/Fill valve and 
a  hole  from  the  return  Drain/Fill  valve  to  a 
suitable visible drain point. 

6.

 

Open No. 1 flow and return valve. Turn on the 
water, allow the all the air to purge through the 
circuit until clear. 

7.

 

When  satisfied  there  is  no  more  air  in  circuit 
No. 1. Close the return valve of No. 1 circuit. 

8.

 

Simultaneously  close  the  flow  valve  of  circuit 
No. 1 and open the flow valve of circuit No. 2. 
Then open the return valve of No. 2 to repeat 
the purging of air in that circuit. 

9.

 

 Repeat steps 4 to 6 until all circuits have been 
purged  of  air.  At  this  point  the  whole  system 
should be full of water and all the circuit valves 
closed. 

10.

 

Check  that  the  main  flow  and  return  pipes 
from the manifold to the boiler connections are 
full of water by purging air from temporary air 
bleed  valves  fitted  to  the  capped  ends  at  the 
boiler location

.  

8.4.2 Pressure testing the system

11.

 

The system should be filled with water   and bled of 
all  air  though  the  air  bleed  valves  fitted  to  the 
manifolds and the main pipes to the boiler. (Refer to 
filling the system 8.4.1 above).

 

12.

 

DO NOT USE COMPRESSED AIR

13.

 

Pressure  test  the  system  with  the  aid  of  a  test 
bucket  and  pressure  gauges,  to  ensure  that  the 
system is free of any leaks. 

14.

 

Proceed as follows:- 

15.

 

Open all flow and return valves. 

16.

 

Fill  pressure  pump  and  connect  to  system  at  a 
convenient point out side of the concrete pour area. 

17.

 

Apply pressure to 6 Bar to the system.  

18.

 

Check all joins for leaks. 

19.

 

Re  pressurise  the  system  until  the  pressure 
remains stable. 

20.

 

Note  that  the  test  pressure  will  be  affected  by 
ambient  temperature  changes.  A  10

o

C  change 

corresponds to a 0.5 – 1.0 Bar pressure variation. A 
normal settled gauge pressure of between 3.5 and 
4.5 Bar during testing would be satisfactory. 

21.

 

Leave  the  system  under  pressure  with  a  visible 
pressure gauge during the concrete pour to ensure 
that  any  leaks  caused  by  an  improper  concrete 
pour are quickly found. 

22.

 

Check to see if the system is under pressure prior 
to the pour and note the pressure at the gauge

Summary of Contents for TIEMME

Page 1: ... be significant Ultimate Comfort Rooms can be heated to different temperatures according to their usage Zones can be set to heat rooms at different times to eliminate cold rooms often during a relative short period of usage The floors are always comfortably warm no matter what the floor coverings are Quiet Operation Tiemme radiant floor heating systems operate without noise and draughts Air moveme...

Page 2: ...f u l l y 1 0 INTRODUCTION 3 2 0 RADIANT UNDER FLOOR HEATING 4 3 0 HEAT LOSS CALCULATIONS 6 4 0 PLANNING LAYING OUT THE SYSTEM 11 5 0 USEFUL INFORMATION 1 5 0 USEFUL INFORMATION 12 6 0 SELECTING A HEAT SOURCE 13 7 0 INFORMATION FOR THE BUILDER 15 8 0 HOW IT IS INSTALLED 16 9 0 MANIFOLD SYSTEM 20 10 0 EXPANSION VESSELS SIZING 24 11 0 FLOOR COVERINGS 25 12 0 HOW IS IT OPERATED 26 13 0 OTHER FORMS OF...

Page 3: ...m Coil length 120 300 600M Volume content l 100M Weight kg 100M Bending radius at 20oC 14 diameters Oxygen diffusion Barrier EVOH The COBRAPEX pipe with oxygen barrier EVOH is made of high density polyethylene chemically cross linked silani reticulation The COBRAPEX pipe reticulation is type b PE Xb this process modifies the chemical structure in order to Increase the maximum working temperature 9...

Page 4: ...a cooler surface Our human comfort relies just as much on radiant heat transfer as it does on air temperature yet the majority of heating and air conditioning professionals think only in terms of air temperature As a result Australians are missing the ultimate comfort available from radiant floor heating in their own homes or places of business By controlling both the air temperature and the radia...

Page 5: ...s such will be suitable for floor coil heating It is important that a uniform cover be maintained between the top of the pipe and slab surface to ensure even floor temperature Minimum cover 30mm Maximum cover 50mm Minimum slab thickness 100mm The following information is to be provided at selection stage 1 Tiemme Cobra Pex pipe specified 2 Pipe dimensions 16 dia x 2 0 wall 3 Pipe spacing 4 Require...

Page 6: ...ration has to be made for the floor coverings to be used The most efficient materials to use for floor coverings are those that have a high rate of conduction a low thermal resistance thus can conduct the heat from the floor and radiate its warmth to you As a rule a maximum R value of 0 15m2K W is best for the floor covering The following table illustrates more common floor covering materials Actu...

Page 7: ... Insulation Compacted Fill Consolidated Earth Tiemme pipe Heated Room 3 1 2 Slab construction Examples of slab constructions are detailed below Moisture Barrier Compacted Fill Consolidated Earth Distance from top of pipe to surface of concrete Maximum 65 mm Minimum 30 mm Pip FIG 1 General installation Heated Room Pip FIG 1 General installation Heated Room ...

Page 8: ...f each method of construction should be considered by the heating engineer and your builder before construction commences FIG 2 pipe in slab with insulation Consolidated earth Concrete slab Moisture Barrier Insulation Polyethylene membrane Mortar Bed Tiles Screed Tiemme pipe FIG 3 Pipe in Screed installation Heated Room ...

Page 9: ...4 50 21 6 41 22 9 33 24 4 24 25 7 200 56 19 0 46 21 3 37 22 6 30 24 1 22 25 6 250 51 18 6 41 20 9 34 22 4 27 23 9 20 25 4 300 45 18 2 37 20 6 30 22 1 24 23 7 18 25 2 Calculate the heat output at various room and water flow temperature of 35oC Floor covering Pipe spacing Room temp 15oC Room temp 18oC Room temp 20oC Room temp 22oC Room temp 24oC mm W M2 Floor oC W M2 Floor oC W M2 Floor oC W M2 Floo...

Page 10: ...0 28 7 250 85 21 0 75 23 3 68 24 8 61 26 3 60 27 8 300 75 20 3 66 22 7 60 24 3 54 25 8 48 27 4 Calculate the heat output at various room and water flow temperature of 45oC Floor covering Pipe spacing Room temp 15oC Room temp 18oC Room temp 20oC Room temp 22oC Room temp 24oC mm W M2 Floor oC W M2 Floor oC W M2 Floor oC W M2 Floor oC W M2 Floor oC Masonry tiles 50 215 30 4 194 31 8 180 33 7 165 33 7...

Page 11: ...ating on the perimeter of the building to increase the comfort of the room FLO W RETU RN d System DLocalising the heat distribution Whatever system A C is used where possible avoid placing piping under places such as kitchen cupboards refrigerators and also in the bathroom Heat can be concentrate for an airing cupboard or sitting area This all makes Tiemme underfloor heating system a most practica...

Page 12: ...ing 30kPa Velocities and pressures above this will cause noise erosion and circulation problems This will depend on the type of circulator used the project conditions and function 5 2 Heat load calculator The following formula can be used to calculate the heat load of the room Room Length x width x height x Factor 1000 Where factor for bedrooms 40 for living rooms 50 Using the same example room a ...

Page 13: ...se can be categorised as the following TYPE D Condensing boilers These boilers offer the highest efficiency and are ideal for the low water temperatures required by the Tiemme floor heating system This type of gas boiler is easy to plumb and control and is highly recommended TYPE B Cast iron boiler Long lasting simple control system easy to plumb and control TYPE A Storage boiler Usually with dome...

Page 14: ...y of the Tiemme floor heating system giving a far better heat distribution than a direct air heater of similar capacity Simple to install and control Type D plumbing 3 Electric heat pumps These water heaters provide the efficiency of the refrigeration multiplier to give excellent running costs where natural gas is not available Further efficiency can be gained by using ground or water sourced heat...

Page 15: ...heck who is responsible for the installation of the insulation if specified 3 Mains water must be available for the flushing and pressure testing of the system 4 Any structural requirements are to be adhered to 5 No go zones for the piping are to be marked out with YELLOW LINES on the prepared site 7 2 Shopping list parts required for the project Item Description Quantity required Make Model size ...

Page 16: ...o the laying Tiemme pipes 2 Fix the header firmly in at the selected position preferably in the centre of the system in a cupboard storage room laundry room linen room or utility room 3 Cover the manifold to ensure that it is not damaged by wet concrete during the pour 4 Mark the manifold with the name of each circuit i e lounge bedroom 2 3 etc 5 Lay out the polystyrene insulation over site 6 Clea...

Page 17: ...t of entry and exit from the slab 6 Start the circuit installation from the header out to the room entering and exiting the selected room through the doorways only 7 The length of all circuits should be approximately the same ideally each circuit should be the full length of the pipe coil 100 metre 8 3 Construction expansion joints Where expansion joints in the concrete are required as part of the...

Page 18: ...aneously close the flow valve of circuit No 1 and open the flow valve of circuit No 2 Then open the return valve of No 2 to repeat the purging of air in that circuit 9 Repeat steps 4 to 6 until all circuits have been purged of air At this point the whole system should be full of water and all the circuit valves closed 10 Check that the main flow and return pipes from the manifold to the boiler con...

Page 19: ...ete floor 12 To minimize the possibility of accidental puncturing of pipes during the construction of the building the pipes should be marked on the concrete in areas where this could happen 13 If it is not possible to keep the system under pressure during the concrete pour then the system should be pressure tested again immediately after the pour has been completed 8 7 Commissioning of the system...

Page 20: ...n module valve Module system allows up to 15 circuits per manifold Valves built in to the manifold saving installation time Easy to extend later System can be installed left or right hand Easy connection to Multitherm pipe Custom made wall brackets Each module is manufactured from high temperature resistant fibreglass reinforced polyamide Temperature resistant from 20oC to 200oC Maximum operating ...

Page 21: ...e instructions carefully before commencing the assembly of the manifold Items required Item No Circuits 3 4 5 6 7 8 9 10 11 12 13 14 Part No No of Items required Starting Kit 6040 1 1 1 1 1 1 1 1 1 1 1 1 Flow Module 6042 3 4 5 6 7 8 9 10 11 12 13 14 Return Module 6045 3 4 5 6 7 8 9 10 11 12 13 14 Compression Fitting 6022 6 8 10 12 14 16 18 20 22 24 26 28 Isolation Valve 2 2 2 2 2 2 2 2 2 2 2 2 Cab...

Page 22: ...RESSURE LOSS Flow 1 2 3 4 5 T o t a l M a n i f o l d F l o w L H 30 66 108 150 180 300 400 500 600 700 800 900 L M 0 5 1 1 1 8 2 5 3 0 5 0 6 7 8 3 1 0 0 1 1 6 1 3 3 1 5 L S 0 008 0 018 0 030 0 417 0 5 0 0 8 0 1 1 0 1 3 0 1 7 0 1 9 0 2 2 0 2 5 Refer to Chart above for flows and pressure loss Pressure M Bar 20 40 60 80 1 0 0 1 2 0 1 4 0 Pressure kPa 2 4 6 8 1 0 1 2 1 4 ...

Page 23: ... e e l c a b i n e t w i t h d o o r S i z e s V K 6 5 0 0 5 0 0 w i d e 5 c i r c u i t s V K 6 7 0 0 7 3 0 w i d e 9 c i r c u i t s V K 6 7 0 0 9 7 0 w i d e 1 4 c i r c u i t s Reduce number of manifold circuits by two circuits if ball valves are used inside the cabinet All pipes should enter from the base and should not touch the sides of the cabinet as this may lead to noise during heating a...

Page 24: ...llowance between 5 and 10 of this value 5 Modern boilers usually have a build in expansion vessel of 7 10L capacity 6 Add an additional expansion to the return leg of the pipe work if the boiler expansion vessel is inadequate In operation this usually shows with boiler pressure of 3 Bar and water flowing through the pressure relief valve Australian Hydronic Supplies Pty Ltd is able to provide supp...

Page 25: ... for a minimum of 30 days 6 To ensure that all parquetry floors or other timber floor coverings are thoroughly kiln dried to eliminate shrinkage It is recommended that timber floor surfaces be laid whilst the heating system is operating 7 When laying timber flooring store the material in the room with the heating turned on To reduce the effects of shrinkage the moisture content of the wood must no...

Page 26: ...en the central room thermostat senses changes in room temperature from the set points 12 3 Multi zone control By placing an additional room clock thermostat in each of a number of zones electric valves fitted to the Multitherm manifolds for selected room circuits can be turned to low off or normal at pre determined times and temperatures 12 4 Climate controlled Using a modern Condensing Boiler and...

Reviews: