Features and functions of actuator controls
●
Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
●
2 multi-colour indication lights:
-
End position CLOSED (yellow), fault/failure (red), end position OPEN (green), operation mode
LOCAL (blue)
Local controls (option)
●
Switch-off mode adjustable:
-
Limit or torque seating for end positions OPEN and CLOSED
●
Torque monitoring across the whole travel
●
Torque by-pass
●
EMERGENCY behaviour programmable:
-
Digital input low active
-
Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN
●
Positioner:
-
Position setpoint via analogue input E1 = 0/4 – 20 mA
-
Programmable behaviour on loss of signal
-
Automatic adaptation of dead band (adaptive behaviour selectable)
-
Switch-over between OPEN - CLOSE control (REMOTE OPEN-CLOSE) and setpoint control
(REMOTE SETPOINT) via digital MODE input
Functions
Plug/socket connector with crimp connection
Standard:
Electrical connection
TPCM-AF1--A70-510AIM110-000
Open-close
duty:
Wiring diagram (basic version)
TPCM-AF1--G7--000AIM110-000
Modulating
duty:
Service conditions
Any position
Mounting position
–25 °C to +70 °C
Ambient temperature
Up to 100 % relative humidity across the entire permissible temperature range
Humidity
IP68
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: maximum 8 m head of water
●
Duration of continuous immersion in water: Max. 96 hours
●
Up to 10 operations during continuous immersion
●
Modulating duty is not possible during continuous immersion
Enclosure protection according to
EN 60529
Pollution degree 4 (when closed), pollution degree 2 (internal)
Pollution degree according to
IEC 60664-1
2 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
Without
Standard:
Shock resistance
●
WTD: in accordance with BV 0430[2] for surface vessels (180 g)
●
WTD: in accordance with BV 0430[2] for submarines (400 g)
●
Shock load up to 70 g
Options:
Sea water resistant bronze housing.
All external screws and shafts are made of stainless steel.
Actuator corrosion protection
(bronze)
Suitable for use in areas with high salinity, almost permanent condensation, and high pollution due to
double layer powder coating. This complies with category C5-M.
Corrosion protection for actuator
controls
Bronze
Actuator:
Colour
AUMA silver-grey (similar to RAL 7037)
Actuator con-
trols:
20,000 operating cycles OPEN - CLOSE - OPEN
An operating cycle is based on an operation from CLOSED to OPEN and back to CLOSED,
at a respective rotary movement of 90°.
Open-close
duty:
Lifetime
5 million modulating steps
Modulating
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve
the modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the
number of starts per hour chosen should be as low as permissible for the process.
47
SG 04.2 – SG 10.2
with actuator controls MEC 03.1
Technical data