7.
Commissioning
Commissioning is made in four steps:
1.
End stop setting
2.
End position setting
3.
Position indicator setting
4.
Configuration of further parameters
Besides end position settings, all other settings have already been made in
the factory in compliance with the order.
If correctly ordered, only end position setting is required.
The following table shows the most important parameters and how they can be
configured.
Page
AUMA CDT
AUMA Assistant
App
At the actuator
Parameter/desig-
nation
Setting
Step
No
No
Yes
End stop CLOSED
Swing angle limita-
tion
End stop setting
No
No
Yes
End stop OPEN
page 26, Set end
position CLOSED
Yes
Yes
Yes
End position
CLOSED setting
Positions
End position set-
ting
Yes
Yes
Yes
End position OPEN
setting
page 28, Position
indicator setting
No
No
Yes
Indication end posi-
tion CLOSED
Indication for the
end positions
Position indicator
setting
No
No
Yes
Indication end posi-
tion OPEN
—
Yes
Yes
No
End position
CLOSED
Type of seating
Configuration of
further parameters
Yes
Yes
No
End position OPEN
Yes
Yes
No
Tripping torque
CLOSE
Torque switching
Yes
Yes
No
Tripping torque
OPEN
Yes
Yes
No
Operating time
Speeds
—
Yes
Yes
No
Type and assign-
ment
I/O signals (bin-
ary/analogue)
—
Yes
Yes
No
Various paramet-
ers
Positioner
Many further parameters can be configured using the AUMA Assistant App or AUMA
CDT. Refer to Manual (Operation & Setting ) PROFOX.
7.1.
End stops in part-turn actuator
The following description applies for clockwise closing standard version.
Separate instructions are available for counterclockwise special version.
The internal end stops limit the swing angle. They protect the valve in case of limit
switching failure during motor operation and serve the purpose as limitation for
23
PF-Q80 – PF-Q600
Commissioning