Operation manual Profibus PBD 100
23.07.2007
19/36
8
Process representation output
Via the process representation output, the master (control) can control the slave (actuator).
Only one operation bit may be set at any given time. If several operation bits are set at the same time, the actuator stops and signals the
fault “wrong command”
Bit
Designation
Value
Description
0
Remote OPEN
1
0
Run OPEN
Do not Run OPEN
1
Remote CLOSED
1
0
Run CLOSE
Do not Run CLOSE
2
Remote NOMINAL
1
0
Run to nominal value Can only be set if position transmitter
(potentiometer / ESR (options)) is available.
Do not run to nominal value
Bits 3-7 are reserved for extensions and must be set to 0.
Byte 2: Nominal output speed: This byte is not used
Value range: 0..100:
Minimum speed: 0 (actuator runs with min. set output speed)
Maximum output speed: 100 (actuator runs with max. set output speed)
Byte 3: Set point (position) high byte
Conditions Values
Parameter 2 (data code from position
transmitter) = 0
This byte must be set to 0.
Parameter 2 (data code from position
transmitter) = 1
This byte states the higher value part (High byte)
of the nominal value.
Byte 4: Set point (position) low byte
Conditions Values
Parameter 2 (data code from position
transmitter) = 0
Range 0..100
Parameter 2 (data code from position
transmitter) = 1
This byte states the lower value part (Low byte) of
the nominal value.
-
-
-
Remote NOMINAL
-
-
Remote CLOSED
Remote OPEN
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Byte 1: Command
Byte 2
Speed
Byte 3
Set point position
high byte
Byte 4
Set point position
low byte
Spare
Byte 5
Spare
Byte 6
Spare
Byte 7
Spare
Byte 8
Byte 1: Commands
Operation bits and
digital outputs