Operation manual Profibus PBD 100
23.07.2007
13/36
Start of stepping distance in direction OPEN. Indication of position in per mil This value must be smaller than the value in parameter 30
(stepping end OPEN in per mil). Otherwise the parameter set will be rejected. This parameter is only effective if parameter 26 (stepping
direction OPEN active) is not 0.
Parameter 30 “Stepping end OPEN in per mil”
Default value: 1000
lowest value: 1
highest value: 1000 (Stepping mode in direction OPEN ends at position 1000 end position OPEN)
End of stepping distance in direction OPEN. Indication of position in per mil This value must be higher than the value in parameter 29
(stepping start OPEN in per mil). Otherwise the parameter set will be rejected. This parameter is only effective if parameter 26 (stepping
direction OPEN active) is not 0.
Parameter 31 “Stepping direction CLOSE active”
Default value: 0
0: Stepping mode in direction CLOSE switched off
1: Stepping mode in direction CLOSE switched on
This parameter is only effective if parameter 1 (position transmitter) is not 0. Otherwise the parameter set will be rejected.
Parameter 32 “Stepping operating time CLOSE in 0.1 s”
Default value: 10
lowest value: 1 (Actuator runs 0.1 s per stepping period)
highest value: 36000 (Actuator runs 1 hour per stepping period)
Operating time for stepping mode in direction CLOSE. Indication in 0.1 seconds. This parameter is only effective if parameter 31 (stepping
direction CLOSE active) is not 0.
Parameter 33 “Stepping pause time CLOSE in 0.1 s”
Default value: 50
lowest value: 1 (Actuator stationary 0.1 s per stepping period)
highest value: 36000 (Actuator stationary 1 hour per stepping period)
Pause time for stepping mode in direction CLOSE. Indication in 0.1 seconds This parameter is only effective if parameter 31 (stepping
direction CLOSE active) is not 0. Otherwise the parameter set will be rejected.
Parameter 34 “Stepping start CLOSE in per mil”
Default value: 1000
lowest value: 1
highest value: 1000 (Stepping mode in direction CLOSE starts at position 1000, end position OPEN)
Start of stepping distance in direction CLOSE. Indication of position in per mil. This value must be higher than the value in parameter 35
(stepping end CLOSE in per mil). Otherwise the parameter set will be rejected. This parameter is only effective if parameter 31 (stepping
direction CLOSE active) is not 0.
Parameter 35 “Stepping end CLOSE in per mil”
Default value: 0
lowest value: 0 (stepping mode in direction CLOSE ends at position
0, end position CLOSED)
highest value: 999
End of stepping distance in direction CLOSE. Indication of position in per mil. This value must be higher than the value in parameter 34
(stepping start CLOSE in per mil). This parameter is only effective if parameter 31 (step-ping direction CLOSE active) is not 0. Otherwise,
the total parameter set will be rejected.
Parameters 36 to 50 are spare parameters.
They are reserved for extensions.
Default value: 0
Value range: 0 to 65535