2016
- GEB1602LG59
AIR CURTAINS
INSTALLATION AND MAINTENANCE MANUAL
E
- 72.529 -
Control panel SC.4951
Connection terminals
DDC-release :
terminals 1 + 11 GND
open = no release
Thermocontact :
Terminals 2 + 12 GND
open = motor error
Frostprotection
: terminals 3 + 13 GND
open = frostprotection activated,
fans OFF,
motorized valve OPEN
Doorcontact
:
terminals 4 + 14 GND
open = fans OFF,
eventual shut-off delay
time ON
Roomthermostat cool-down protection :
terminals 5 + 15 GND
open = no function
Terminals 6 + 16 GND & 7 + 17 GND
not in use
8
9
error notification contacts
10
18
19
20
operation notification contacts
towards
next steering
unit
towards
control
panel
motorized valve
connection
motorized valve
connection
motor
address
steering u.
shut /off
delay
operation notification
contacts
error notification contacts
Room thermostat cool down protection
Door contact
Frost protection
Motor protection
BMS release
1 x 230V
50Hz
to control input next air curtain
SC.4951
servomotor
silver
control panel