Figure 2

 

 

To prevent moisture from entering inside of coach, apply RTV 
type sealant to the back of the bezel flange of the vent part. 

 

Vents are designed to allow water drainage when installed 
correctly. 

 

Vents are design to allow for different wall thickness up to a 
maximum of 2-

1/2”  

 

1. 

Locate vent hole cutout as called out in Figure 2. 

2. 

Drill 3-

1/2” diameter hole through sidewall of coach maximum wall 

thickness 2-

1/2”. 

3. 

Remove vent and vent ring from furnace. 

4. 

Insert furnace from backside of wall, lining up hole in wall with 
vent in furnace. 

5. 

Apply sealant to back of vent ring. 

6. 

Install vent assembly with HOT at top on horizontal installations 
and HOT on right side for vertical installations.  Vent ring must slip 
inside combustion air intake tube. Secure to wall with 2 screws 
not provided. 

7. 

Vent assembly must maintain minimum overlap of 1-

1/4” on 

exhaust tube and 1/2” minimum on combustion air tube. DO NOT 
exceed maximum wall thickness. 

8. 

Secure furnace to floor with legs provided on back of casing. For 
vertical units casing legs can be positioned for placement to 
secure furnace 

 

STANDARD DOOR INSTALLATION 

 

Figure 3 

 

 

To prevent moisture from entering inside of coach, apply RTV 
type sealant to all sealing areas. 

 

The door bezel must fit tightly, to prevent water leakage. 

 

Doors are designed to allow water drainage in either horizontal or 
vertical installations. Proper location of vent assembly is important 
for proper exhausting of fumes and proper function of furnace. 
 

1. 

Cut hole opening as shown in Figure 3 in location of side wall 
were unit will be installed. 

2. 

Apply RTV type sealant to entire back flange of bezel creating a 
sealing area. 

3. 

Pull furnace forward through cutout about a 1” inch, slip bezel 
around casing, and flush inner flange with casing.  

4. 

Secure bezel to furnace casing with 6 screws. 

5. 

Push furnace and bezel back tight against side wall and secure 
with 14 screws. 

6. 

When installing screws DO NOT deform bezel. 

7. 

Connect the gas line to the valve and push the gas line plug into 
casing opening.  

8. 

Remove excess sealant from around bezel and visually inspect 
bezel to make sure it is completely sealed. 

9. 

Secure furnace to floor with mounting legs provided.  

10.  Fasten door and vent with 6 screws provided. 

 

INTERIOR GRILL INSTALLATION 

 

Figure 4 

 

Figure 5 

 

To install grill cut an 11” x 7.25” hole into the cabinet for a non-
removable furnace installation. See Figure 4 

 

To install grill as an access to remove furnace cut a 12-

1/2” x 8-3/4” 

hole into the cabinet from the floor up you must also purchase a trim 
ring for this installation. See Figure 5 

 

Interior grill supplies return air and heated air necessary for AFSA 
models and must be used. All other AFS models this grill is an option. 

 

Discharge air from the round center louver can be direct 360° by tuning 
louver.  
 

1. 

Locate furnace and cut opening in outside wall as shown in figure 1. 

2. 

To install grill for front discharge remove the knockout from the rear of 
the casing 

and attached the 5” duct adapter.  

3. 

Fasten 5” ducting to the adapter and to the back of the interior grill and 
secure. 

4. 

On installation with 1” or less space between furnace and cabinet face 
grill can be inserting into the adapter ring to complete the connection. 

5. 

Secure grill to cabinet by fastening with two screws through mounting 
holes or if optional trim ring secure first with four screws to the cabinet 
then the grill to the trim ring. 

6. 

Vertical installation cutout and space see Table 5 for dimensions. 

DUCTING OPTIONS 

REQUIRED MINIMUM DISCHARGE 

Models 

Required Discharge Area 

AFSDA 

FRONT GRILL ONLY 

AFSD 

24 in

2

 

Summary of Contents for AFSAD12111

Page 1: ...DO NOT use furnace cabinet area as a storage compartment DO NOT vent furnace with venting system serving another appliance DO NOT vent furnace to an outside enclosed porch area DO NOT use for temporary heating of buildings or structures under construction Protect building materials from degrading from flue gas exhaust Protect furnace electrical components from water Compartments must be closed whe...

Page 2: ...cted 12 Volt Amperage AMPS 3 4 3 4 4 8 2 4 Power Supply Volt DC 12 12 12 12 Watts 41 41 56 34 Minimum Return Air 35 in2 35 in2 35 in2 35 in2 WC WATER COLUMN DUCTING CONFIGURATION Table 2 Models AFSD12 AFSD16 AFSD20 AFSAD12 Side Ducting 2 Ducts 2 Ducts 2 Ducts N A Front with Side Ducting 1 or 2 Ducts 1 or 2 Ducts 1 or 2 Ducts N A Front Only no Side Ducts Front Front Front Front DIMENSION Table 3 Ap...

Page 3: ...ition CAUTION Due to the differences in vinyl siding materials this appliance should not be installed without first consulting with the manufacturer of the siding or cutting the siding away from the area around the appliance vent A gas fired furnace for installation in a residential garage must be installed so the burner s and the ignition source are located not less than 18 in 457mm above the flo...

Page 4: ...h cutout about a 1 inch slip bezel around casing and flush inner flange with casing 4 Secure bezel to furnace casing with 6 screws 5 Push furnace and bezel back tight against side wall and secure with 14 screws 6 When installing screws DO NOT deform bezel 7 Connect the gas line to the valve and push the gas line plug into casing opening 8 Remove excess sealant from around bezel and visually inspec...

Page 5: ...d PROPANE GAS CONNECTION Propane Gas Pressure Test The furnace and any individual shut off valve must be disconnected from gas supply piping system during and pressure testing of system at test pressures of more than 1 2 PSI Before furnace is connected piping systems are to be tested to be leak free The test must maintain air pressure of a least 6 of mercury or 3 PSI for at least 10 minutes The en...

Page 6: ... and remain off until unit is reset by reactivating the thermostat Stop Read Users Information Manual supplied with furnace 1 Turn the manual valve if so equipped or the valve at the outside LP tank to the OFF position Do NOT force NOTE This furnace is equipped with a valve shut off switch with switch in OFF position Gas will not flow to burner nor will the furnace operate Turn switch to ON positi...

Page 7: ...7 WIRING AND LADDER DIAGRAM ...

Page 8: ...8 PART DRAWINGS PART LISTS ...

Page 9: ...9 ...

Page 10: ...10 ...

Page 11: ...lorsque vous effectuez le test NE PAS utiliser un courant alternatif de 120 V avec les modèles à courant continu NE PAS utiliser la zone du cabinet de fournaise comme compartiment de rangement NE PAS aérer la fournaise avec un système de ventilation pour entretenir un autre appareil NE PAS aérer la fournaise à un endroit extérieur fermé comme une véranda NE PAS utiliser pour le chauffage temporair...

Page 12: ...S ÉLECTRIQUES 6 INSTALLATION DU THERMOSTAT 6 INSTRUCTIONS D UTILISATION 6 POUR METTRE HORS TENSION 7 VÉRIFICATIONS DU SYSTÈME 7 SPÉCIFICATIONS MODÈLE Tableau 1 Nos de modèles AFSD12 AFSD16 AFSD20 AFSAD12 Type de gaz LP Propane LP Propane LP Propane LP Propane BTU en entrée 12 000 16 000 18 000 12 000 BTU en sortie 9 120 12 160 13 680 9 120 Conduit de pression statique 0 10 po WC 0 10 po WC 0 10 po...

Page 13: ...souples installez la fournaise sur des taquets ou sur un panneau de bois ou de métal s étendant de la largeur et profondeur complète de la fournaise plus un dégagement minimal pour les combustibles NE PAS utiliser de nettoyant à base de pétrole ou de type citron sur les pièces de plastique vous pourriez les endommager ATTENTION À cause des différences dans les matériaux de revêtement en vinyle cet...

Page 14: ...e dans le calfeutrage et inspectez visuellement le conduit pour vous assurer qu il est bien scellé fixez avec deux conduits et deux vis et retirez l excès de calfeutrage INSTALLATION STANDARD DE LA PORTE Figure 3 Toutes les surfaces en contact avec l extérieur du mur latéral doivent être étanches et scellées avec un scellant RTV Les conduits sont conçus pour permettre l évacuation d eau lorsqu ins...

Page 15: ...s de tuyauterie flexible Suivez les configurations de tuyauterie dans le tableau 2 Évitez des extrémités tranchantes ou des conduits écrasés Étirez tous les conduits et branchez les directement aux sorties gardant la quantité et les angles de tuyaux pliés au minimum 1 Retirez le plateau de déboucheur des sorties désirées See Figure 6 Si les deux sorties de 4 po ne sont pas utilisées laissez les en...

Page 16: ...19 17 11 16 87 65 52 43 37 33 29 26 17 Cette fournaise est conçue pour une mise à la terre négative de 12 V à courant continu seulement NE PAS essayer de modifier la fournaise pour un système de mise à la terre positif ou connecter la fournaise directement à un courant alternatif de 120 V Les dommages sur les composantes de la fournaise se produiront et la garantie sera annulée Utilisez un fil de ...

Page 17: ... éteignez l unité et contactez votre revendeur ou une agence locale de véhicules récréatifs Ne pas continuer faire fonctionner la fournaise par le thermostat espérant avoir une ignition POUR METTRE HORS TENSION 1 Mettez le thermostat au réglage le plus bas puis déplacez le levier dans la position ARRÊT 2 Tournez la valve manuelle d arrêt si équipé à la position ARRÊT Ne pas forcer VÉRIFICATIONS DU...

Reviews: