PACK Status Normal/Alarm/Protection
RUN
ALM
Remark
Sleep
Power Off
OFF
OFF
All off
Standby
Normal
Alarm
Flash 1
Flash 1
OFF
Flash 3
Standby state
Cell low voltage
Charge
Normal
Alarm
Over Charge protection
Temperature/Over current
Fault/Protection
The maximum power LED
flashes (flashes 2), and the
overcharge alarm ALM
does not flash
ON
ON
ON
OFF
Flash 3
OFF
OFF
ON
If there is no mains power,
LED as standby
Close charge
Discharge
Normal
Alarm
Under Discharge
Protection
Temperature/Over current
Short circuit/Fault/Protection
OFF
Flash 3
Flash 3Flash 3
ON
OFF
OFF
OFF
ON
Close discharge
Close charge/discharge
Fault
HMI Screen: There are 2LEDS on front panel to show the battery working status.
HMI light flashing mode is the same as LCD light flashing mode.
5.2.5 Sleep and wake up
When any of the following conditions is met, the system enters the low power
consumption mode:
◆
Single or overall over discharge protection is not released within 30 seconds.
◆
Press the key (3 ~ 6S) and release the key.
◆
The minimum monomer voltage is lower than the sleep voltage, and the duration
reaches the sleep delay time (no communication, no protection, no balance and
no current).
◆
The standby time exceeds 24 hours (no communication, no charge and discharge,
no mains power).
◆
Forced shutdown by upper computer software.
Sleep:
Explanation
Before entering sleep, ensure that the input terminal is not connected to the external
voltage, otherwise it will not be able to enter the low power consumption mode.
Notice
23