![Atlas Copco QAS 500 Volvo S2A APP Instruction Manual Download Page 96](http://html1.mh-extra.com/html/atlas-copco/qas-500-volvo-s2a-app/qas-500-volvo-s2a-app_instruction-manual_3001967096.webp)
- 96 -
Derating table (in %, 100% is declarated power at “Performance data”)
50 Hz
Notes
1)
Reference conditions for engine performance to ISO 3046-1.
2)
See derating diagram or consult the factory for other conditions.
3)
At reference conditions unless otherwise stated.
4)
Rating definition (ISO 8528-1):
LTP: Limited Time Power is the maximum electrical power which a generating set is capable of delivering (at variable load), in the event of a
utility power failure (for up to 500 hours per year of which a maximum of 300 hours is continuous running). No overload is permitted on these
ratings. The alternator is peak continuous rated (as defined in ISO 8528-3) at 25°C.
PRP: Prime Power is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per
year, between stated maintenance intervals and under the stated ambient conditions. A 10% overload is permitted for 1 hour in 12 hours. The
permissible average power output during a 24h period shall not exceed the stated load factor of 70%.
5)
Specific mass fuel used: 0.86 kg/l.
Height
(m)
Temperature
(°C)
0
5
10
15
20
25
30
35
40
45
50
0
100
100
100
100
100
100
100
100
100
90
80
500
100
100
100
100
100
100
100
100
100
90
80
1000
100
100
100
100
100
100
100
100
100
90
80
1500
100
100
100
100
100
100
100
95
95
90
80
2000
95
95
95
95
95
95
95
95
90
90
80
2500
90
90
90
90
90
90
90
85
85
80
80
3000
85
85
85
85
85
85
85
85
85
80
80
3500
65
65
65
65
65
65
65
65
65
65
65
4000
50
50
50
50
50
50
50
50
50
50
50
Summary of Contents for QAS 500 Volvo S2A APP
Page 1: ...QAS 500 Volvo S2A APP Instruction Manual for AC Generators English...
Page 2: ......
Page 99: ...99 Circuit diagrams...
Page 112: ......
Page 113: ......
Page 114: ...Printed in Belgium 05 2009 2954 3870 00 www atlascopco com...