- 74 -
(optional)
mobile/E
mobile/E
Mounting
fully resilient
fully resilient
Climatic exposure
open air
open air
Degree of protection (cubicle)
IP 54
IP 54
Status of neutral (ELR-config.) (optional)
earthed
earthed
Status of neutral (IT-config.) (optional)
insulated
-
Alternator 4)
Standard
IEC34-1
IEC34-1
ISO 8528-3
ISO 8528-3
Make
Leroy Somer
Leroy Somer
Model
LSA 40M5
LSA 40M5
Rated output, class H temp. rise
20.0 kVA
25.0 kVA
rating type acc. ISO 8528-3
BR
BR
Degree of protection
IP 23
IP 23
Insulation stator class
H
H
Insulation rotor class
H
H
Number of wires
12
12
Engine 4)
Standard
ISO 3046
ISO 3046
ISO 8528-2
ISO 8528-2
Type KUBOTA
V2403M-BG
V2403M-BG
Rated net output
18.8 kW
22.1 kW
rating type acc. ISO 3046-7
ICXN
ICXN
production tolerance
± 5%
± 5%
Coolant
coolant
coolant
Combustion system
direct injection
direct injection
Aspiration
natural aspirated
natural aspirated
Number of cylinders
4
4
Swept volume
2.4 l
2.4 l
Speed governing
electronic
electronic
Capacity of oil sump
9 l
9 l
Capacity of cooling system
9 l
9 l
Electrical system
12 Vdc
12 Vdc
Emission compliance
EU STAGE II