- 28 -
If a special status has elapsed, the active view will be
entered again automatically.
If an Alarm comes up, the Alarm Display is shown.
Parameter list
The Parameter Menu's are pre-programmed !
A password will be asked for when an attempt to
change a setting is about to be done (user password =
2003).
By entering the parameter list, pushbutton
AUTOMATIC is disposed of its normal operations
and will not perform any functionality.
It's possible to scroll between configuration menu's
by using the pushbuttons UP and DOWN.
Pushing the ENTER button activates the
configuration menu which is shown at the display.
Menu's shown on the Parameter list LCD:
Genset mode
This menu is used to change the mode of the machine.
In the Qc2002™ module 2 application modes can be
selected:
Island operation
– This operation type is selected for local/remote
start applications, without the Mains (= stand-
alone).
• Combined with Manual Operation mode =
Local Start operation.
• The sequences start/stop/close Generator
Contactor / open Generator Contactor can be
activated manually.
• Combined with Automatic Operation mode =
Remote Start operation.
– The remote start signal can be given with an
external switch. After the generator has been
started, the Generator Contactor will close
automatically.
– Installation wirings for Remote Start operation:
wire the RS switch between X25.9 & X25.10.
Automatic Mains Failure (AMF) operation
– This application is only possible in combination
with the Auto mode. If the Manual Operation
mode is selected the AMF operation will NOT
function !
– When the Mains exceeds the defined voltage /
frequency limits for a defined delay time, the
generator will take over the load automatically.
– When the mains is restored within the defined
limits for a defined time, the generator will unload
before disconnecting and switching back to the
Mains.
– The generator will then go into cooldown and
stop.
– Installation wirings: we refer to circuit diagram
9822 0992 79/02 for the correct connections.
Horn delay
This menu is used to set the delay, how long the
general alarm relay stays energized (if present). If set
to 0.0s, the general alarm relay will stay energized
continuously.
Genset Mode
Island Island AMF
Horn Delay
0.0s 20.0s 990.0s