“Element 1 Outlet”
103˚C
.
“Shutd. Warn.” “Maximum”
100˚C
“Menu”***
***
F1
F2
F3
• The screen indicates that the temperature at the outlet of compressor element 1 exceeds the programmed
shut-down warning level.
• If necessary, stop the compressor by means of stop button (4) and wait until it has stopped.
• Switch off the voltage, inspect and remedy.
• The warning message will disappear automatically as soon as the warning condition disappears.
A service warning exists
• LED (1) is alight. The Main screen will change into a screen similar to the one below:
“Compressor Outlet”
7.0 bar
.
“*Service Required*”
“Menu”***
***
F1
F2
F3
• The indicators (***) are blinking and the service warning message appears.
• Press the key Menu (F1) and the tabulator key (2) to select the “Status data” menu: the option “Service”
is blinking.
• Scroll to this option and select it by pressing the tabulator key (2); two options may blink:
• “Inputs”: if the programmed service level of a component is exceeded (e.g. the maximum pressure
drop of the air filter).
• “Plan”: if a service plan interval is exceeded.
• Stop the compressor and switch off the voltage.
• In case the service message was referring to “Inputs” (air filter): replace the filter, switch on the voltage,
scroll in the “Status Data” menu to “Inputs” and press the “Reset” key to reset the service message.
• In case the service message was referring to “Plan”: carry out the service actions related to the indicated
plans. Reset the timers of the related plans. Contact your Atlas Copco Customer Centre. See
Instruction book
52
2920 1728 05
Summary of Contents for GA 110 VSD
Page 1: ...GA 110 VSD GA 132 VSD GA 160 VSD Instruction book ...
Page 2: ......
Page 17: ...Rear view of air cooled GA Instruction book 2920 1728 05 15 ...
Page 23: ...Air cooled compressors Instruction book 2920 1728 05 21 ...
Page 30: ...Instruction book 28 2920 1728 05 ...
Page 31: ...Instruction book 2920 1728 05 29 ...
Page 32: ...Instruction book 30 2920 1728 05 ...
Page 33: ...Instruction book 2920 1728 05 31 ...
Page 34: ...Instruction book 32 2920 1728 05 ...
Page 35: ...Instruction book 2920 1728 05 33 ...
Page 36: ...Instruction book 34 2920 1728 05 ...
Page 79: ...Dimension drawing of air cooled Full Feature VSD compressors Instruction book 2920 1728 05 77 ...
Page 100: ...Instruction book 98 2920 1728 05 ...
Page 101: ...Instruction book 2920 1728 05 99 ...
Page 103: ...Figure A Instruction book 2920 1728 05 101 ...
Page 104: ...Figure B Instruction book 102 2920 1728 05 ...
Page 107: ...Text on figure Instruction book 2920 1728 05 105 ...
Page 164: ......
Page 165: ......