Important
The readings mentioned below are valid under the reference conditions (see section
Reference conditions and limitations
).
Reference
Reading
Air outlet pressure
Depends on the setpoint (desired net pressure).
Compressor element
outlet temperature
Approx. 65 ˚C (117 ˚F) above ambient temperature.
9.2
Electric cable size
Attention
• The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage.
It is however highly recommended to keep the voltage drop over the supply cables at
nominal current below 5% of the nominal voltage (IEC 60204-1). If cables are grouped
together with other power cables, it may be necessary to use cables of a larger size
than those calculated for the standard operating conditions.
• Use the original cable entry. See section
.
To preserve the protection degree of the electric cubicle and to protect its components
from dust from the environment, it is mandatory to use a proper cable gland when
connecting the supply cable to the compressor.
• Local regulations remain applicable if they are stricter than the values proposed
below.