71
A03- Sx80/S100/S120/
Battery Low
11.0V ± 0.5VDC
Battery CutOFF
10.0V ± 0.5VDC
Battery Charging Voltage
13.8V ± 0.4VDC
A03-S1001/S1501/S2001
Battery Low
22.2V ± 0.5VDC
Battery CutOFF
20.0V ± 0.5VDC
Battery Charging Voltage
27.6V ± 0.4VDC
AVR
Vin(V)
AVR
Vout(V)
Note
Vin
≦
160V
N/A
Inv (220± 10%)
the UPS returns to AC
output mode when AC
input increase to 170V
160V
≦
Vin
≦
190V
Increase (18%)
190-224V
Vout(min)=190V
190V
≦
Vin
≦
250V
N/A
Vin
250V
≦
Vin
≦
290V
Decrease (18%)
212-245V
Vout(max)=245V
Vin
≧
290V
N/A
Inv (220± 10%)
The UPS returns to AC
output mode when AC
input drops to 280V