Voltage Range (Online Mode)
Vin(V)
Action
Vout(V)
Note
Vin
≦
160 ± 5%
Switch to Battery
Mode
INV Battery (220±
1%)
the UPS returns to
AC output mode
when AC input
increase to 175V
(5%)
166V
≦
Vin
≦
300V
Online Mode
INV AC (220± 1%)
Vin
≧
300± 5%
Switch to Battery
Mode
INV Battery (220±
1%)
The UPS returns to
AC output mode
when AC input drops
to 290V (5%)
Voltage Range (ECO Mode)
Vin(V)
Action
Vout(V)
Note
Vin
≦
LLS
Switch to Battery
Mode
INV Battery (220±
1%)
Vout - 7Vac
<LLS<
Vout -24 Vac
LLS
≦
Vin
≦
HLS
ECO Mode
Vout=Vin
Vin
≧
HLS
Switch to Battery
Mode
INV Battery (220±
1%)
Vout + 7Vac
<HLS<
Vout +24 Vac
Voltage Range (ByPass Mode)
Vin(V)
Action
Vout(V)
Note
Vin
≦
LLS
Switch to Battery
Mode
INV Battery (220±
1%)
170Vac
<LLS<
220Vac
LLS
≦
Vin
≦
HLS
ByPass Mode
Vout=Vin
Vin
≧
HLS
Switch to Battery
Mode
INV Battery (220±
1%)
230Vac
<HLS<
264Vac