3.3 UPS Setting
LED6 LED7 LED8 LED9 LED10
LED1 LED2 LED3 LED4 LED5
Press and hold
Select
button for 5 seconds to enter UPS setting mode when UPS is
in standby mode or bypass mode. Press
On/Mute
or
Select
to display next/previous
selection in UPS setting mode.
LED3 flashing: Output voltage setting
Interface
Setting
For 200/208/220/230/240 VAC models, you may
choose the following output voltage:
LED7:
presents output voltage is 208Vac
LED8:
presents output voltage is 220Vac
LED9:
presents output voltage is 230Vac
LED10:
presents output voltage is 240Vac
LED4 flashing: Bypass enable/disable when UPS is off
Interface
Setting